4.14.6 MATCHING AND SCALING A CURRENT TRANSDUCER

Example:
Given a 0 - 150-PSI transducer with a 4-20 mA output.

Program the OM-550 to indicate 0 - 150 PSI with 0.01-PSI resolution.

If the 4-20 mA Current Probe is being used, begin with step 2, below. (This probe is
already matched to the OM-550).

1. First, find the Matching resistor:

R1

= 2 / I

=

2 / 20 mA

=

2 / 0.02

=

100

When the transducer output is 4 mA, the OM-550 will see 0.4 VDC and when the
transducer output is 20 mA, the OM-550 will see 2 VDC.

2. Next, find m & b:

X1

= 0.4000 VDC

ç minimum expected input

=

4000 A/D counts

at Transducer minimum output

X2

= 2.0000 VDC

ç maximum allowable input

=

20000 A/D counts

at Transducer maximum output

Y1

= 0.00 PSI

ç minimum transducer output

=

0.00 PSI

ç choose decimal point = 2

Y2

= 150.00 PSI

=

15000 display counts

m

= (Y1 - Y2) / (X1 - X2)

=

(0 - 15000) / (4000 - 20000)

=

0.93750

b =

Y2 - (m * X2)

=

15000 - (0.93750 * 20000)

= -003750

Notice the decision to indicate with 0.01-PSI resolution determined a decimal position
of 2.