TOA Electronics CST38MH User Manual

Page 19

Advertising
background image

19

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Figure 46

hearth extension dimensions

a

16"

b

8-1/"

c

8"

d

44-1/"

methods of determining hearth extension and wall shield

equivalents -

To determine the thickness required for the alternate

material when either the "k" value or "r" value is known, use either the

k formula or r formula.
example: If Micore 160 is to be used for the hearth extension fireplace,

how thick must this material be?

k

M

= k value per inch of alternate material

r

M

= r value per inch of alternate material

T

M

= minimum thickness required for alternate material

T

s

= standard thickness of the alternate material

k

L

= k value per inch of listed material

r

L

= r value per inch of listed material

T

L

= minimum thickness of listed material

Note: An asterix "*" indicates, it is a value taken from Table 5.

using the k formula:

minimum

k-value (per Inch) of

specified min.

thickness of = alternate material (k

M

) x

thickness

alternate

k-value (per inch)

of listed

material (T

M

)

of listed material (k

L

)

material (T

L

)

T

m

(inches) =

k

m

x

T

l

*.84

T

m

(inches) = *.35

x

1"

*.84

.416 (inches)=

.416

x

1"

Answer - The minimum required thickness of the Micore 160 is .417," there-

fore round up to nearest standard thickness available which is 1/2."

minimum

r-value (per Inch)

specified min.

thickness of = of listed material

x

thickness

alternate

r-value (per inch)

of listed

material

of alternate material

material

T

m

(inches) =

r

l

x

T

l

r

m

T

m

(inches) = *1.19 x

1"

* .86

.417 (inches)=

.416

x

1"

Answer - The minimum required thickness of the Micore 160 is .417," there-

fore round up to nearest standard thickness available which is 1/2."

using the r formula:

note: To convert inches to millimeters divide by .03937.

listed material

k (per inch)

r (per inch)

listed min.Thickness

listed material

.84

K

L

1.19

r

L

1

"

T

L

** approved alternate materials for floor/hearth Protection

alternativematerials

Thermal Values

minimumThickness

(rounded to nearest 1/8 inch)

k (per inch)

K

M

r (per inch)

r

M

min. Thickness

T

M

Kaowool m board

.47

.13

.56" (1/")

micore 160™

U.S. Gypsum

.35

.86

.4" (3/8")

micore 300™

U.S. Gypsum

.46

.17

.55" (1/")

durock™ cement board

U.S. Gypsum

1.9

.5

.9" (-1/4")

hardibacker™

1.95

.513

.3" (-3/8")

hardibacker 500™

.30

.435

.74" (-3/4")

cultered stone hearth-

stone™

.8

.355

3.36" (3-3/8")

wonderboard

3.3

.31

3.85" (3-7/8")

super firetemp m

Johns-Manville

.61

1.64

.73" (3/4")

super firetemp l

Johns-Manville

.54

1.85

.64" (5/8")

face brick

9.00

.111

10.71" (10-3/4")

common brick

5.00

.0

5.95" (6")

cement mortar

5.00

.0

5.95" (6")

ceramic tile

1.5

.08

14.88" (14-7/8")

marble

~11

~.09

13.10" (13-1/8")

Table 5

** If the hearth extension material(s) that is intended to be used is NOT listed

on Table 5, the material can still be used if the material(s) is noncombustible.

However, the manufacturer of the material must provide either the listed k-value

per inch or r-value per inch with listed thickness so that the minimum thickness

required for the hearth can be calculated (per instructions on this Page and/or

as specified in the NFI Certification manuals).
Note: Also see NFI (National Fireplace Institute) Certification Manuals showing

other exceptable caluculation methods and acceptable alternate materials

which can be used.

B

A

C

C

Protected

Side Wall

Model CST-38

D

40"

40"

a

b

d

c

c

wall shield required

where less Than 18".

adjacent wall is never

allowed closer

Than 8".

Advertising