NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

3

Figure 1

TyPIcal InsTallaTIon

InTroducTIon

General Information

The CST38MH Series is a radiant-heat, two-

sided fireplace with standard glass doors and

an outside combustion air kit is provided.

A steel grate is also included to properly posi-

tion the fire and limit the amount of fuel. If a

rePlacemenT GraTe Is needed rePlace

The GraTe wITh model sGr-38b only.

Note: Illustrations shown reflect “typical”

installations with nominal dimensions and

are for design and framing reference only.

Actual installations may vary due to individual

design preferences. However, always maintain

minimum clearances to combustible materials

and do not violate any specific installation

requirements.

These fireplaces have been tested and listed

by OMNI Test Labs (Report No. 116-F-20-4) to

U.L. standard 127. These units are intended for

installation in Manufactured Homes, residential

homes and other buildings of conventional

construction including commercial.

These fireplace systems are designed for in-

stallation in accordance with the National Fire

Protection Standard for chimneys, fireplaces

and solid fuel burning appliances; NFPA 211-

latest edition and in accordance with codes

such as the BOCA Basic/National Codes, the

Standard Mechanical Code and the Uniform

Building Codes.

The fireplace opening must be kept a minimum

of 8" (203 mm) from a protected combustible

side wall. A perpendicular side wall can not be

closer that 18" (457 mm). If there is a continu-

ous perpendicular side wall closer than 18" from

the fireplace opening, it must be protected with

a 40" x 40" x 1/2" (1016 mm x 1016 mm x 13

mm) wall shield constructed of a durable non-

combustible material with an equal or greater

insulating value than k=.84 BTU IN/FT2 HR °F

(refer to Pages 18, 19 and 20).

As with all chimney installations, avoid overhead

obstructions such as trees, power lines, etc.

Additionally chimney terminations must meet

certain clearance to roof requirements detailed in

the paragraph titled Ten-Foot Rule Summary.

The fireplace and chimney system must be

enclosed when installed in or passing through

a living area where combustibles or people may

come in contact with it. This is important to pre-

vent possible personal injury or fire hazard.

For questions, please call your distributor or

the manufacturer. Special restrictions apply to

the front and facing of the fireplace and nearby

walls (See Pages 18, 19 and 20).

chImney sysTem

These fireplaces are designed and code listed

for use with Security Chimneys FTF8 chimney

System only. Always use Security Chimneys

FTF8 chimney components with these fireplaces.

Do not modify or alter these components as

this may cause a potential serious hazard and

void the Warranty.

*Construction Materials:

• Framing Materials • Paneling

• Particle Board

• Flooring

• Dry Wall

• Plywood

• Noncombustible Insulating Materials

• Etc.

chimney height

The total height of your Fireplace systems from

the surface the fireplace rests on to the chimney

top must not exceed 80' (24.4m) and must also

meet minimum system height chart.

warnInG

failure to use manufacture

provided parts, variations in

techniques and construction

materials or practices other than

those described in this manual

may create a fire hazard and void

the limited warranty.

warnInG

do not pack or fill required air

spaces with insulation or other

material. no material is allowed

in these areas. secure the

airspace around the chimney

with the firestop/thimble before

completing the installation.

maintain " clearance between

chimney and thimble.

warnInG

If insulation is used, the fireplace

must not be placed directly

against it. Insulation or vapor

barriers, if used, must first be

covered with gypsum board,

plywood, particle board or other

material to assure insulation

and vapor barriers remain in

place.

when complete these fireplace systems con-

sists of four basic “sub-systems”:

1. The fireplace

. The chimney and Termination

3. Glass doors

4. combustion air Kit

clearances and heIGhT

requIremenTs

The fireplace may be placed on or near normal

construction materials*. The combustion air

kit, firestop spacer and roof flashing (not chase

flashings) may be placed directly on or against

normal construction materials.* The chimney

and fireplace outer wrapper require a minimum

2" and 1/2" air space to combustibles respectively.

A combustible mantel may be installed 12" above

the opening of the fireplace as per NFPA 211-

latest edition.

chimney and

Termination

firestop

Thimble

outside combustion air Kit

minimum system height

security's fTf8 Pipe

Vertical Installation

15' 0"

one offsets

16' 0"

Two offsets

5' 0"

Table 1