Caution – TOA Electronics CST38MH User Manual

Page 9

Advertising
background image

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

9

InsTallInG The chImney sysTem

step 1. Check flue damper for proper operation.

To open, push handle up and release.

Damper will open automatically. To

close, pull handle down and release

damper will fall to the closed posi-

tion.

Note: The damper may be operated from both

firebox openings.

cauTIon

allow minimum " (51 mm)

chimney air space to combus-

tible framing members through-

out vertical or offset chimney

installation. also maintain air

space on top of the fireplace

as defined by the spacers and

standoffs.

A minimum 2" (51 mm) air space must be

reserved for all combustible materials extend-

ing for any continuous length surrounding the

chimney.

Reference Figures 15 and 16 on Page 8,

which specify minimum ceiling and roof di-

mensions.

Figure 18 - outside combustion air Kit

Cut or frame a hole through the outside wall for

the installation of the duct inlet hood. A 6 1/2”

(151 mm) diameter hole is sufficient. Feed the

loose end of the flexible air duct through the

hole cut for the inlet hood and attach to collar

on inlet hood using the tie strip provided. Insert

hood into opening. Secure in place with the

No. 8 x 1-1/2” screws provided or with nails

driven through holes in hood flange. Seal with

noncombustible waterproof silicon type caulk-

ing. If additional length of duct is necessary,

purchase locally available Class 0 or Class 1

ducting. The duct may extend up to 50' (15.2

m) in any direction.

Note: Do not terminate combustion air kit in

attic space under any circumstances.

cauTIon

never locate the air inlet where

it could be blocked by shrubs,

leaves, snow drifts, etc. never

locate the air inlet in garage or

any area where there is another

fuel burning appliance or prod-

ucts emitting combustible gases

such as paint, gasoline, etc.

In cold climates, it is recom-

mended that the combustion air

duct be insulated.

cauTIon

In no event may the total duct for

bringing in outside air exceed

50' (15. m).

step . Using standard construction framing

techniques, construct opening for chim-

ney route up through the ceiling(s) and

roof or through an outside chase.

Framing must maintain adequate mini-

mum air space clearance at all times.

Air Inlet Assembly

(Attach To Floor)

Non-Combustible

Class 0 Or Class 1

6 Inch Air Inlet Duct

Actuator

Arm

Clamp

Securely

At Top And

Bottom

Vented Crawl Space