4300 Series Ancillary Cabinets Installation and Operation Manual

7 Storage/Operating Environment

7.1 Storage Environment

Observe the following when storing the ancillary cabinets.

Store ancillary cabinet indoors.

Temperature fluctuations should be minimized.

The optimal storage temperature range is 68 – 77 °F (20 – 25° C).

A maximum temperature range of 32 – 104 °F (0 – 40 °C) should be observed.

The optimal relative humidity at the storage location should be between 50 – 60%.

Humidity must not exceed 90%.

Avoid locations where ancillary cabinet may be exposed to corrosive gas.

Avoid locations with dirt and/or dust.

TABLE 7.1 - UPS STORAGE/OPERATING ENVIRONMENT STANDARDS

Item

Environment standard

Storage Location

Indoors

Ambient Temperature

Minimum storage temperature: 32 °F (0 °C)
Maximum storage temperature: 104 °F (40 °C)

Relative Humidity

The relative humidity must be between 30 and 90% and without

condensation due to temperature changes.

Altitude

This equipment is rated for installations up to 3240 ft. (1000 m)

above sea level. Consult with the factory to determine the derating

factor for installations above 3240 ft. (1000 m).

Dust

Dust must not exceed normal atmospheric levels and must not

include conductive/corrosive particles, silicone or oils.

Flammable Gas

No flammable and/or explosive gas.
Hydrogen sulfide (H

2

S)

Less than or equal to 0.0001 PPM

Sulfurous acid gas (SO

2

)

Less than or equal to 0.05 PPM

Chlorine gas (Cl

2

)

Less than or equal to 0.002 PPM

Ammonia gas (NH

3

)

Less than or equal to 0.1 PPM

Nitrous acid gas (NO

2

)

Less than or equal to 0.02 PPM

Nitrous oxides (NOx)

Less than or equal to 0.02 PPM

Ozone (O

3

)

Less than or equal to 0.002 PPM

Hydrochloric acid mist (HCl) Less than or equal to 0.1 mg/m

3

7.2 Operating Precautions

Initial startup/commissioning of the

ancillary cabinet

should be performed by factory authorized personnel.

1) The

ancillary cabinet

should not be powered up until the entire operation manual has

been read. Follow Lockout/Tag Out procedures.