Toshiba AUXILIARY CABINET 431M User Manual

Page 34

Advertising
background image

26

4300 Series Ancillary Cabinets Installation and Operation Manual

Table 10.3 - 431A

Input/Output Power Cable Sizes

(

Cable sizes for 75°C Copper Cable)

Recommended/Maximum Wire size and

Torque Requirement

Trans

-

former

Code

Input/Output T

rans

-

former V

oltage

Xfmr T

ype

30 kV

A

50 kV

A

Tightening

Torque

Phase A

WG*

Neutral A

WG*

Phase A

WG*

Neutral A

WG*

Input

B

208V

Δ

to

208/120V

Y

Input Iso

2 - 250 kcmil

N/A

2/0 - 250 kcmil

N/A

200 in.-lbs.

C

240V

Δ

to

208/120V

Y

Input Iso

3 - 250 kcmil

N/A

1/0 - 250 kcmil

N/A

200 in.-lbs.

N

380V

Δ

to

208/120V

Y

Input Iso

6 - 250 kcmil

N/A

3 - 250 kcmil

N/A

200 in.-lbs.

N

400/415V

Δ

to

208/120V

Y

Input Iso

6 - 250 kcmil

N/A

3 - 250 kcmil

N/A

200 in.-lbs.

S

480V

Δ

to

208/120V

Y

Input Iso

6 - 250 kcmil

N/A

4 - 250 kcmil

N/A

200 in.-lbs.

M

600V

Δ

to

208/120V

Y

Input Iso

6 - 250 kcmil

N/A

6 - 250 kcmil

N/A

200 in.-lbs.

X

208/120V

Y 4 wire input

(No T

ransformer)

N/A

1/0 - 250 kcmil

4/0 - 350 kcmil

250 kcmil

350 kcmil

200 in.-lbs.

K

480/277V

Y

to

208/120V

Y

Input Auto

6 - 250 kcmil

3 - 350 kcmil

3 - 250 kcmil

2/0 - 350 kcmil

200 in.-lbs.

Output

F

208/120V

Y 4 wire input

(No T

ransformer)

N/A

1/0 - 250 kcmil

4/0 - 350 kcmil

250 kcmil

350 kcmil

200 in.-lbs.

H

208/120V

Y

to

220/127V

Y

Output Auto

1 - 250 kcmil

4/0 - 350 kcmil

4/0 - 250 kcmil

350 kcmil

200 in.-lbs.

J

208/120V

Y

to

240/139V

Y

Output Auto

2 - 250 kcmil

3/0 - 350 kcmil

3/0 - 250 kcmil

350 kcmil

200 in.-lbs.

P

208/120V

Y

to

380/220V

Y

Output Iso

4 - 250 kcmil

1 - 350 kcmil

1 - 250 kcmil

4/0 - 350 kcmil

200 in.-lbs.

Q

208/120V

Y

to

400/230V

Y

Output Iso

4 - 250 kcmil

1 - 350 kcmil

2 - 250 kcmil

3/0 - 250 kcmil

200 in.-lbs.

K

208/120V

Y

to

480/277V

Y

Output Auto

6 - 250 kcmil

3 - 350 kcmil

3 - 250 kcmil

2/0 - 250 kcmil

200 in.-lbs.

M

208/120V

Y

to

600/347V

Y

Output Iso

6 - 250 kcmil

4 - 350 kcmil

4 - 250 kcmil

1/0 - 250 kcmil

200 in.-lbs.

* Wire capacity for Phase lugs is 250 kcmil - 6

AWG, Neutral lugs is 350 kcmil - 6

AWG.