10.9 INSTALLATION INSTRUCTIONS

DANGER: HAZARDOUS VOLTAGES MAY EXIST.

Verify all power is removed from the UPS and power cables prior connecting the power

cables to the Ancillary cabinet terminals, Maintenance Bypass Switch terminals, or UPS

terminals.

The Toshiba Auxiliary Cabinet (431A) can be used in either of two arrangements. 431A with the 4300

UPS, or 431A with the 431M and the 4300 UPS.

431A with the 4300 UPS

Select the proper cable size per Table 10.3 then got to Section

Place the 431A Cabinet.

431A with 431M and 4300 UPS

Select the proper cable size per Table 10.3.
Terminate the cable end connecting to the 431M with 0.5 inch bolt hole terminal lugs. See Table 10.2

below.
The 431M Circuit Breakers are equipped with terminal bus strips pre-drilled in a standard NEMA 2-hole

pattern (0.5 in. bolt holes on 1.75 in. centers) to facilitate installation of power cables. Use of NEMA two-

hole cable terminations is recommended.
Terminate the cable end connecting to the 431M with 0.5 inch bolt hole terminal lugs. See Table 10.2

below.

Table 10.1: Bolt Tightening Specifications

ITEM

Torque

Grade 8, 1/2 in. Bolts

119 ft-lb (161 N•M)

The following table lists examples of NEMA 2-hole compression type fittings.

Table 10.2: Compression Fittings

Ilsco P/N

Description

Conductor Size

Fitting Color

CLND-6-12-134

CSWD -6-12-134

Long Barrel

Short Barrel

#6

Blue

CLND-4-12-134

CSWD -4-12-134

Long Barrel

Short Barrel

#4

Grey

CLND-3-12-134

Long Barrel

#3

White

CLND-2-12-134

CSWD -2-12-134

Long Barrel

Short Barrel

#2

Brown

CLND-1-12-134

CSWD -1-12-134

Long Barrel

Short Barrel

#1

Green

CLND-1/0-12-134

CSWD -1/0-12-134

Long Barrel

Short Barrel

1/0

Pink

CLND-2/0-12-134

CSWD -2/0-12-134

Long Barrel

Short Barrel

2/0

Black

CLND-3/0-12-134

CSWD -3/0-12-134

Long Barrel

Short Barrel

3/0

Orange

CLND-4/0-12-134

CSWD -4/0-12-134

Long Barrel

Short Barrel

4/0

Purple

CLND-250-12-134

CSWD -250-12-134

Long Barrel

Short Barrel

250

Yellow

CLND-300-12-134

CSWD -300-12-134

Long Barrel

Short Barrel

300

White

CLND-350-12-134

CSWD -350-12-134

Long Barrel

Short Barrel

350

Red

Go to Section

Place the 431A Cabinet.