Place the 431B Cabinet.

Table 11.3 - 431B Power Cable Sizes

(

Cable sizes for 75°C Copper Cable)

Recommended/Maximum Wire size and Torque Requirement

UPS

Rating

Maximum DC Current

Recommended Cable

Sizes

UPS Terminal Lug

Tightening Torque

431B Bus Lugs

Tightening Torque

20 kVA

84 Adc

4 AWG – 350 kcmil

200 in.-lbs.

119 ft-lb (161 N•M)

30 kVA

126 Adc

1 AWG – 350 kcmil

200 in.-lbs.

119 ft-lb (161 N•M)

40 kVA

169 Adc

1/0 – 350 kcmil

200 in.-lbs.

119 ft-lb (161 N•M)

50 kVA

210 Adc

4/0 – 350 kcmil

200 in.-lbs.

119 ft-lb (161 N•M)

60 kVA

253 Adc

250 kcmil – 350 kcmil

200 in.-lbs.

119 ft-lb (161 N•M)

* Wire capacity for DC lugs is 350 kcmil - 6 AWG,

11.4 Place the 431B Cabinet

The 431B Cabinet has four mounting holes to anchor the unit after is has been set in place. See Figure

10-3. Use 1/2 in (12 mm) bolts to anchor the 431B.

Verify the Left Side Access Plate of the 431B and the corresponding Right side ac-

cess plate of the 4300 UPS are removed before anchoring the unit.

NOTE: Ensure the 431B can be joined to the UPS before final anchoring of the 431A. Use four 3/8 in.

-16 x 2 in long bolts to bolt the ancillary cabinet frames together.

Back

Front

4 x 0.63 in. Dia. (16 mm)

19.0 in. (483 mm)

26.7 in..

(677 mm)

Figure 11-3 - 431B Base Anchor Points