10.6 Join the Auxiliary Cabinet with the UPS

The Toshiba Auxiliary Cabinet (431A) is equipped with four 14 mm mating holes located on the front and

back of the left and right sides of the cabinet.

1. Remove the top and bottom 431A Cabinet Front panels.

2. Remove the cable access plate at the lower-front right side of the 431A Cabinet. (See Figure 10.5)

3. Remove the cable access plate at the lower-front left side of the UPS Cabinet.

4. Position the 431A cabinet to the left of and adjacent to the UPS Cabinet.

5. Align the four 0.63 in (14 mm) bolt holes on the right side of the 431A Cabinet with the matching four

14 mm bolt holes on the left side of the UPS Cabinet.

6. Bolt the cabinets together with four 3/8-16 in. x 2 in. long bolts.

7. Select the power cables per Table 10.2 /Table 10.3. Cable size for the UTILITY and LOAD terminals

are dependant on the Input/Output Voltages to the transformers. The UPS Input/Output cables will be

the same size: 3Phase/4Wire 208/120V.

8. Run the power cables from UPS power terminals TB1 to 431A Cabinet power terminals TB1 per Fig-

ure 10-6.

9. Run the appropriately sized power cables from 431A TB2 to the Utility and Load per Figure 10-6.

Figure 10-5 - 431A Cable

Access Plate

Figure 10-6 - Power Cabling Between

Auxiliary Cabinet and UPS

Utility Power

L1

L2

L3

N

(Optional)

Critical Load

N

L1

L2

L3

(Optional)

1

431A

TB1

To UPS IN

From Utility

TB2

From UPS OUT

To LOAD

H1 H2 H3 N N L1 L2 L3

H1 H2 H3 N N L1 L2 L3

4300 Series UPS

TB1

H1

H2

H3

N

AC OUT

AC IN

N

L1

L2

L3

+

-

BA

TT