4300 Series Ancillary Cabinets Installation and Operation Manual

8.3 Anchor Bolts

Install the anchor bolts to secure the UPS on the floor. See Figure 8.2 for anchor bolt installation detail.

Use 1/2” (12 mm) diameter anchor bolts. There are four 0.63” (16 mm) diameter holes provided in the

cabinet base. See Figure 8.3A for the hole locations and dimensions for the specified Ancillary Cabinets..

Anchor Bolt

(1/2 in (12 MM))

4 x 0.63 in. (16 mm)

diameter bolt holes

4 bolt holes

(Side View)

FIGURE 8.2 ANCHOR BOLT INSTALLATION DETAIL

FIGURE 8.3A HOLE LOCATIONS/DIMENSIONS ON BOTTOM OF CABINETS

431A/431B

Back

Front

4 x 0.63 in. Dia. (16 mm)

19.0 in. (483 mm)

26.7 in..

(677 mm)

431M

Back

Front

11.0 in. (279 mm)

20.0 in.

(508 mm)

4 x 0.63 in. Dia. (16 mm)

FIGURE 8.3B HOLE LOCATIONS/DIMENSIONS ON SIDES OF CABINETS

A

B

Left Side

A

B

Right Side

Dimensions

A - 29 in. (736 mm)

B - 60 in. (1523 mm)

Use 4 ea. 3/8”x16 2 in

long bolts to join adjacent

UPS /ancillary cabinet

frames. (The left side

of each cabinet has a

3/8”x16 pin nut to receive

the corresponding bolt.)