Jksss+ series 2.3 - 4.2kv – Toshiba VF010H05 User Manual

Page 11

Advertising
background image

JKSSS+ Series - 5

JKSSS+ Series

2.3 - 4.2KV

• Contactors: Vacuum contactors are provided for both In-Line Isolation and SCR

Bypass. The contactor voltage ratings are: 7.2kV for 2300 - 6900V units.

A sequencing feature controls the contactors. Under normal operating conditions

this ensures that both contactors make and break under no-load conditions to

maximize contactor life. Vacuum contactors are rated for the maximum starting

requirement of the unit design. The Bypass Contactor is rated to be capable

of emergency start. For further information on the vacuum contactor, see the

instruction manual on the vacuum contactor supplied with the equipment, and

also either VF010H01 (400A Drawout Type) or VF010H03 (Fixed Type).

• Soft Start Only Option: The JKSSS+ Series is also offered in an optional “Soft

Start Only” package for use in retrofitting behind an existing customer supplied

line start controller. In this configuration,

the Disconnect Switch, Fuses and

Line Isolation Vacuum Contactor are NOT included in the JKSSS+ unit, so

proper interlocking of sections containing medium voltage becomes the install-

er’s responsibility.

All retrofit “Soft Start Only” packages must be used with complete line isola-

tion using a contactor or other “air-gap” device. The Optional “Soft Start Only”

includes overload protection in normal operation mode and will sequence the

isolation contactor, so all logic control should be done at the JKSSS+ control

unit. Avoid turning the JKSSS+ on and off using the isolation device.

1.4 Structure and Power Bus

The JKSSS+ Series is a heavy duty design. Special consideration has been given

to the enclosure and unit design to ensure that it is suitable for most applications and

environments.

• Structure: 11 gauge frame with 16 gauge side, back and top sheets. Doors are

12 gauge steel. The enclosure assembly is NEMA / EEMAC type 1 as standard.

Type 12 and 3R are available as an option.

• Sections: In a typical arrangement, each enclosure is divided vertically into

three major compartments, each with a separate door. In the JK400, the upper-

most and lowermost compartments contain medium voltage controller compo-

nents (>600V) while the middle compartment contains low voltage components

(<600V). Other variations of this basic arrangement are possible.

The

Main Incoming Power Compartment houses the main disconnect switch,

amain power fuses and input isolation contactor. A viewing window provides

clear indication of the switch position without opening the compartment.

Main

Bus Compartment contains the horizontal bus bars (if provided). Top, bottom or

side cable entry can be made with minimum bending.

One or more

Starter Power Compartments contain the bypass vacuum con-

tactors, SCR power modules, instrument transformers and all other medium

voltage devices. Adequate room is provided for motor lead connections to be

made with minimum conductor bend.

A

Low Voltage Control Compartment houses the digital microprocessor

controller and LCD keypad operator interface, along with any other low voltage

devices. This allows the operator to make adjustments without exposure to the

line voltages.