Jksss+ series 2.3 - 4.2kv – Toshiba VF010H05 User Manual

Page 26

Advertising
background image

JKSSS+ Series - 20

JKSSS+ Series

2.3 - 4.2KV

2.9.1 - Incoming Line

On the Standard JKSSS, incoming power cable connections should be made at the

points shown on the wiring diagram furnished with the equipment.

Note: Proper phase sequence must be observed when connecting the input power.

For example, phase A must lead phase B, which in turn must lead phase C by 120°

respectively. If the phase rotation is not correct, a fault light and the LCD display will

indicate the problem. The SCR output will be clamped.

2.9.2- Load Connections

The load cables should be routed through the wireways furnished within the enclosure.

Load cable termination arrangements, refer to the drawings furnished with the equip-

ment.

2.9.3- Ground Connections

The controller line-up must be grounded in accordance with the requirements of the Na-

tional Electrical Code. Proper equipment grounding must be established before making

any incoming power connection. If a main ground bus is furnished, make the ground con-

nection to this bus. If there is no ground bus, the sections which are shipped separately

should be connected in such a way as to ensure a continuous grounding path.

Each section contains a vertical ground bus extending from the main ground bus or ground

pad to each controller compartment.

Special attention should be paid to protection for operating personnel, to protection of

equipment itself, (i.e. such as ground fault relays, if used) and protection of sensitive

transducers or control devices that are electronic in nature.

The following may be used as a general guide with regard to equipment grounding.

Controller used as service equipment for a grounded system or as a main section for a

seperately derived system:

a. The grounding electrode conductor (ground wire) sized in accordance with NEC 250

should be run from the grounding electrode to the controller ground bus or ground

terminal.

b. Unless already done at the factory, a main bonding jumper should be installed from

the incoming grounded connector bus (neutral) to the ground bus or designated

grounding point. If a jumper is not furnished, one having a size in accordance with

NEC 250 should be selected.

c. Steps (a) and (b) should effectively connect together the grounding electrode, the

controller frame, all outgoing equipment grounding conductors and the grounded

neutral bus of the system.

d. No connection should be made to ground on the load side of any neutral disconnecting

line or any sensor used for ground fault protection. No connections should be made

between outgoing grounding connectors and the neutral.

e. Where the controller or system is dual-fed (double-ended) and has ground fault

protection, special precautions are necessary to accomplish proper grounding and

bonding.

Advertising