Jksss+ series 2.3 - 4.2kv, Menu – Toshiba VF010H05 User Manual

Page 68

Advertising
background image

JKSSS+ Series - 62

JKSSS+ Series

2.3 - 4.2KV

SP.8 Overload Curve Configuration (Setpoint Page 8)

(Security Level: 3)

SP8.3 Area Under Curve Protection: If enabled, this

secondary start protection uses both the basic start

protection and the area under the curve protection.

• Max I*I*T Start: The maximum I

2

T allowed during

start. If the I

2

T to start exceeds this number then the

soft starter will generate a trip.

SP8.4 Current Over Curve: Learns the motor’s starting

characteristics and protects the motor based upon

the learned curve. It is useful when commissioning a

new motor.

Learn: The unit reads the motor’s starting

characteristics. Start the motor and allow it to come

to full speed. The start feedback enables the motor

protection based on the learned start curve.

• Learned Start Curve Basis: The maximum allowed

deviation above or below the start curve before a trip

is generated.

• Time for Sampling: The time the soft starter

continues to sample the start curve characteristic

during learn the mode.

MENU

PAGE 8 OVERLOAD
CURVE CONFIGURATION

BASIC RUN
OVERLOAD CURVE

(Hit DOWN ARROW seven times)

RUN CURVE LOCKED
ROTOR TIME: O/L CLASS

Range: 1 - 30 SEC, O/L CLASS

RUN LOCKED ROTOR
CURRENT: 600% FLA

BASIC START
OVERLOAD CURVE

AREA UNDER CURVE
PROTECTION: DISABLED

CURRENT OVER
CURVE: DISABLED

Range: ENABLED or DISABLED

Options: DISABLED, LEARN
or ENABLED

COAST DOWN TIMER
TIME: DISABLED

START CURVE LOCKED
ROTOR TIME: O/L CLASS

NUMBER OF STARTS PER
HOUR: DISABLED

TIME BETWEEN STARTS
TIME: 5 MIN

MAX I*I*T START
: 368 FLA*FLA*SEC

ACCELERATION TIME
LIMIT: 30 SEC

LEARNED START CURVE
BIAS: 10%

Range:1 - 60 MIN, DISABLED
Increments of 1

Range:1 - 30 SEC, O/L CLASS
Increments of 1

Range:1 - 300 SEC, DISABLED
Increments of 1

Range: 1 - 6, DISABLED
Increments of 1

Range:1 - 60 MIN, DISABLED
Increments of 1

Range:1 - 2500, FLA*Time (Sec)
Increments of 1

Range: 5 - 40%
Increments of 1

START LOCKED ROTOR
CURRENT: 600% FLA

TIME FOR SAMPLING
: 30 SEC

Range: 400 - 800%
Increments of 10

Range: 1 - 300 SEC
Increments of 1

Range: 400 - 800%
Increments of 1

Configures the unit’s start and

run protection mode. The unit has

independent start and run curve

protection and the settings can be

based on the OL Class or set by the

motor’s locked rotor current and time.

SP8.1 Basic Run Overload Curve

• Run Curve Locked Rotor

Time: Set the locked rotor time

to the OL Class default chosen

in Setpoint Page 1 or set the

time in seconds. This is the

time the locked rotor condition

exists before a trip occurs.

• Run Locked Rotor Current:

The current the motor draws

with full voltage on the windings

and no rotor movement (as a

percent of motor FLA). Refer to

the nameplate data or contact

the motor manufacturer.

• Coast Down Timer: If enabled,

this prevents the motor from

restarting for the programmed

amount of time, after a stop

command is given.

SP8.2 Basic Start Overload Curve

• Start Curve Locked Rotor Time: The locked

rotor time can be set to the OL Class default

chosen in Setpoint Page 1 or to a specific

time. The overload condition must exist for the

programmed amount of time before a trip occurs.

• Start Locked Rotor Current: The current the

motor draws with full voltage on the windings and

no motor movement (as a percent of motor FLA).

Refer to the motor nameplate data or contact the

motor manufacturer.

• Acceleration Time Limit: If the motor does not

enter run mode (reach at speed) within the preset

time, the unit trips on acceleration time limit.

• Number of Starts per hour: If enabled, this

limits the maximum number of starts permitted per

hour. This setpoint allows a maximum of 6 starts

per hour. Contact motor manufacturer.

• Time Between Starts: If enabled, the soft

starter prevents another start attempt until the

programmed time has expired.