Jksss+ series 2.3 - 4.2kv – Toshiba VF010H05 User Manual

Page 49

Advertising
background image

JKSSS+ Series - 43

JKSSS+ Series

2.3 - 4.2KV

5.1.9 RTD Configuration Page 9 Cont’d

5.1.10 Security Set Password Page 10

5.1.11 Communications Page 11

Setpoint

Page

Security

Level

Description

Factory Setting

Default

Range

Section

RTD #10 Type

Off

Same as Stator Phase A1

RTD #10 Description

User defined

User defined, Up to 15 Characters

RTD #10 Alarm Level

Off

0-240C (32-464F), Off

RTD #10 Trip Level

Off

0-240C (32-464F), Off

RTD #11 Type

Off

Same as Stator Phase A1

RTD #11 Description

User defined

User defined, Up to 15 Characters

RTD #11 Alarm Level

Off

0-240C (32-464F), Off

RTD #11 Trip Level

Off

0-240C (32-464F), Off

RTD #12 Type

Off

Same as Stator Phase A1

RTD #12 Description

User defined

User defined, Up to 15 Characters

RTD #12 Alarm Level

Off

0-240C (32-464F), Off

RTD #12 Trip Level

Off

0-240C (32-464F), Off

Page

9

RTD Configuration

Level

3

Password Protection

SP9.4

Setpoint

Page

Security

Level

Description

Factory Setting

Default

Range

Section

Set Level 2 Password

100

000 – 999 Three Digits

SP10.1

Set Level 3 Password

1000

0000 – 9999 Four Digits

SP10.2

Page

10

Level

3

Setpoint

Page

Security

Level

Description

Factory Setting

Default

Range

Section

Set Front Baud Rate

9.6 KB/sec

2.4, 4.8, 9.6, 19.2, 38.4 KB/sec

SP11.1

Set Modbus Baud Rate

9.6 KB/sec

2.4, 4.8, 9.6, 19.2, 38.4 KB/sec

SP11.2

Modbus Address Number

247

1 – 247

SP11.3

Set Access Code

1

1 – 999

SP11.4

Set Link Baud Rate

38.4 KB/sec

2.4, 4.8, 9.6, 19.2, 38.4 KB/sec

SP11.5

Remote Start/Stop

Disabled

Enabled or Disabled

SP11.6

Page 11

Communiications

Level

3

Password Protection