• When the motor reaches full speed, the “AUX4” LED (At Speed) will be lit.

The POWER, RUN, AUX3 LEDs will be lit, indicating that the contact has

energized. IA, IB, IC will display the current setting for Phase A, Phase B,

and Phase C and the G/F indicates ground fault. (Display 4)

• If the motor decelerates, or stops, during the acceleration period, hit the

stop button immediately and open the disconnect line. If the unit does not

follow this operational sequence, please refer to the Troubleshooting Chapter.

It is best to operate the motor at its full load starting condition to achieve the proper

time, torque and ramp settings. Initial settings are set to accommodate most motor

conditions.

TRy INITIAL SETTINGS FIRST. See Section 5.1.1 (Setpoint Page 2) to

make any adjustments.

• Initial Voltage

• Soft Start Curve

• Current Limit

• Acceleration Time

If decel is enabled, the following parameters for Deceleration Time, Start Decel Volt-

age (see SP2) and Stop Decel Voltage (see SP2) must also be programmed.

3.6 Emergency Bypass Operation

Remove input power (using line start section and lock out disconnect).

• Close the emergency bypass contact.

• Re-close the disconnect on line start panel.

• If integral overload protection is not to be used (see JP-1 Motor Protection

Jumper), then bimetallic or solid state overload protection is required

(customer supplied if factory emergency overload protection option has not

been included.)

IN THE EMERGENCy ByPASS MODE, THERE IS NO

OVERLOAD PROTECTION UNLESS A SEPARATE

(OPTIONAL OR CUSTOMER SUPPLIED) THERMAL OR SOLID

STATE OVERLOAD RELAy IS INSTALLED, OR jP-1 (MOTOR

PROTECTION jUMPER) IS REMOVED FROM THE TCB BOARD.

The line start panel is operable as a normal across-the-line starter. When

power is applied, the bypass contactor is energized, tying the input terminals

directly to its output terminals. When the “ON/OFF” contact is closed, the

main contactor is energized and the motor line starts. When the “ON/OFF”

contact is opened, the motor is disconnected from the line via the main in-line

vacuum contactor.

MOTOR STOPPED
READY TO START

MOTOR STARTING
00 X FLA

OVERLOAD ALARM
TIME TO TRIP: XXX SECS.

IA: _ _ _ IB: _ _ _
IC: _ _ _ G/F: _ _ _

Display 1

Display 2

Display 3

Display 4

DANGER

HAZARDOUS OPERATION

Do not operate the Bypass Contactor with medium
voltage power applied to the unit.

Failure to follow this instruction will cause the motor
to start unexpectedly.

!