Jksss+ series 2.3 - 4.2kv – Toshiba VF010H05 User Manual

Page 43

Advertising
background image

JKSSS+ Series - 37

JKSSS+ Series

2.3 - 4.2KV

5.1.3 Phase and Ground Settings (Setpoint Page 3)

* Ground fault option must be installed.

Setpoint

Page

Security

Level

Description

Factory Setting

Default

Range

Section

Imbalance Alarm Level

15% FLA

5-30 %, Off

Imbalance Alarm Delay

1.5 sec

1.0-20.0 sec

Imbalance Trip Level

20%

5-30 %, Off

Imbalance Trip Delay

2.0 sec

1.0-20.0 sec

Undercurrent Alarm Level

Off

10-90 %, Off

Undercurrent Alarm Delay

2.0 sec

1.0-60.0 sec

Overcurrent Alarm Level

Off

100-300 %, Off

Overcurrent Alarm Delay

2.0 sec

1.0-20.0 sec

Overcurrent Trip Level

Off

100-300 %, Off

Overcurrent Trip Delay

2.0 sec

1.0-20.0 sec

Phase Loss Trip

Enabled

Enabled or Disabled

Phase Loss Trip Delay

0.1 sec

0-20.0 sec

Phase Rotation Detection

ABC

ABC, ACB or Disabled

Phase Rotation Trip Delay

1.0 sec

1.0 - 20.0 sec

*Ground Fault Alarm Level

Off

5-90 %, Off

*Ground Fault Alarm Delay

0.1 sec

0.1-20.0 sec

*Ground Fault Loset Trip Level

Off

5-90 %, Off

*Ground Fault Loset Trip Delay

0.5 sec

0.1-20 sec

*Ground Fault Hiset Trip Level

Off

5-90 %, Off

*Ground Fault Hiset Trip Delay

0.008 sec

0.008-0.250 sec

Overvoltage Alarm Level

Off

5 -30%, Off

Overvoltage Alarm Delay

1.0 sec

1.0-30.0 sec

Overvoltage Trip Level

10%

5-30%, Off

Overvoltage Trip Delay

2.0 sec

1.0-30.0 sec

Undervoltage Alarm Level

Off

5-30%, Off

Undervoltage Alarm Delay

1.0 sec

1.0-30.0 sec

Undervoltage Trip Level

15%

5-30%, Off

Undervoltage Trip Delay

2.0 sec

1.0-30.0 sec

Line Frequency Trip Window

Disabled

0-6 Hz, Disabled

Line Frequency Trip Delay

1.0 sec

1.0-20.0 sec

P/F Lead P/F Alarm

Off

0.1-1.00, Off

P/F Lead Alarm Delay

1.0 sec

1-120 sec

P/F Lead P/F Trip

Off

.01-1.00, Off

P/F Lead Trip Delay

1.0 sec

1-120 sec

P/F Lag P/F Alarm

Off

.01-1.00, Off

P/F Lag Alarm Delay

1.0 sec

1-120 sec

P/F Lag P/F Trip

Off

.01-1.00, Off

P/F Lag Trip Delay

1.0 sec

1-120 sec

Power Demand Period

10 min

1 - 60 min

KW Demand Alarm Pickup

Off KW

Off, 1-100000

KVA Demand Alarm Pickup

Off KVA

Off, 1-100000

KVAR Demand Alarm Pickup

Off KVAR

Off, 1-100000

Amps Demand Alarm Pickup

Off Amps

Off, 1-100000

Page

3

Phase and Ground Settings

Level

2

Password Protection

SP3.1

SP3.2

SP3.3

SP3.4

SP3.5

SP3.6

SP3.7

SP3.8

SP3.11

SP3.12

SP3.18

SP3.20

SP3.13

SP3.14

SP3.15

SP3.9

SP3.10

SP3.19

SP3.17

SP3.16

Advertising