Jksss+ series 2.3 - 4.2kv, Menu – Toshiba VF010H05 User Manual

Page 56

Advertising
background image

JKSSS+ Series - 50

JKSSS+ Series

2.3 - 4.2KV

SP.3 Phase & Ground Settings

(Setpoint Page 3)

(Security Level: 2)

MENU

PAGE 3 PHASE &
GROUND SETTINGS

IMBALANCE ALARM
LEVEL: 15% FLA

Range: 5 - 30%, OFF
Increments of 1

(Hit DOWN ARROW two times)

IMBALANCE ALARM
DELAY: 1.5 SEC.

Range: 1.0 - 20.0 SEC.
Increments of 0.1

IMBALANCE TRIP
LEVEL: 20%FLA

OVERCURRENT ALARM
LEVEL: OFF

Range: 5 - 30%, OFF
Increments of 1

Range: 100 - 300%, OFF
Increments of 1

IMBALANCE TRIP
DELAY: 2.0 SEC.

OVERCURRENT ALARM
DELAY: 2.0 SEC.

Range: 1.0 - 20.0 SEC.
Increments of 0.1

Range: 1.0 - 20.0 SEC., OFF
Increments of 0.1

OVERCURRENT TRIP
LEVEL: OFF

PHASE LOSS TRIP
: ENABLED

Range: 100 - 300%, OFF
Increments of 1

Options: Enabled or Disabled

OVERCURRENT TRIP
DELAY: 2.0 SEC.

PHASE LOSS TRIP
DELAY: 0.1 SEC.

Range: 1.0 - 20.0 SEC.
Increments of 0.1

Range: 0 - 20.0 SEC.

Options: ABC, ACB or
Disabled

Range: 1.0 - 20.0 SEC.

Increments of 0.1

UNDERCURRENT ALARM
LEVEL: OFF

Range: 10 - 90%, OFF
Increments of 1

UNDERCURRENT ALARM
DELAY: 2.0 SEC.

Range: 1.0 - 60.0 SEC.
Increments of 0.1

PHASE ROTATION
DETECTION: ABC

GROUND FAULT LOSET
TRIP LEVEL: OFF

Range: 5 - 90%, OFF
Increments of 1

PHASE ROTATION TRIP
DELAY: 1.0 SEC

GROUND FAULT LOSET
TRIP DELAY: 0.5 SEC

Range: 0.1 - 20.0 SEC.
Increments of 0.1

GROUND FAULT HISET
TRIP LEVEL: OFF

Range: 5 - 90%, OFF
Increments of 1

GROUND FAULT HISET
TRIP DELAY: 0.008 SEC.

Range: 0.008 - 0.250 SEC.
Increments of 0.002

GROUND FAULT ALARM
LEVEL: OFF

Range: 5 - 90%, OFF
Increments of 1

GROUND FAULT ALARM
DELAY: 0.1 SEC.

Range: 0.1 - 20.0 SEC.
Increments of 0.1

OVERVOLTAGE ALARM
LEVEL: OFF

OVERVOLTAGE ALARM
DELAY: 1.0 SEC.

Range: 5 - 30%, OFF
Increments of 1

Range: 1.0 - 30.0 SEC.
Increments of 0.1

OVERVOLTAGE TRIP
LEVEL: 10%

OVERVOLTAGE TRIP
DELAY: 2.0 SEC.

Range: 5 - 30%, OFF
Increments of 1

Range: 1.0 - 30.0 SEC.
Increments of 0.1

UNDERVOLTAGE ALARM
LEVEL: OFF

UNDERVOLTAGE ALARM
DELAY: 1.0 SEC.

Range: 5 - 30%, OFF
Increments of 1

Range: 1.0 - 30.0 SEC.
Increments of 0.1

UNDERVOLTAGE TRIP
LEVEL: 15%

UNDERVOLTAGE TRIP
DELAY: 2.0 SEC.

Range: 5 - 30%, OFF
Increments of 1

Range: 1.0 - 30.0 SEC.
Increments of 0.1

LINE FREQUENCY TRIP
WINDOW: DISABLED

LINE FREQUENCY TRIP
DELAY: 1.0 SEC.

Range: 0 - 6, Disabled
Increments of 1

Range: 1.0 - 20.0 SEC.
Increments of 0.1

*

*

*

Note: Proper phase sequence must be observed when

connecting the input power. For example, phase A

must lead phase B, which in turn must lead phase

C by 120° respectively. If the phase rotation is

not correct, a fault light and the LCD display will

indicate the problem.

SP3.1 Imbalance Alarm Level: This is an advance warning

of a phase imbalance problem. The problem may

not be a fault in the motor, but merely caused by

imbalanced voltages.

• Imbalance Alarm Delay: The amount of time the

imbalance condition must exist before an alarm

occurs.

SP3.2 Imbalance Trip Level: This will trip the motor on

excessive phase imbalance. The trip level should

be programmed to a higher value than the alarm

level.

• Imbalance Trip Delay: The amount of time the

imbalance condition must exist before a trip will

occur.

SP3.3 Undercurrent Alarm Level: Typically used to warn

of possible load loss, a coupling breaking or other

mechanical problems.

• Undercurrent Alarm Delay: The amount of time

the undercurrent condition must exist before an

alarm will occur.

SP3.4 Overcurrent Alarm Level: Typically used to indicate

when the motor is overloaded. This feature can be

used to either stop the feed to the equipment or

warn operators of an overload condition.

• Overcurrent Alarm Delay: The amount of time the

overcurrent condition must exist before an alarm

will occur.

Advertising