JKSSS+ Series - 46

JKSSS+ Series

2.3 - 4.2KV

SP.1 Basic Configuration (Setpoint Page 1)

In Setpoint Page 1, the starter is looking for the following basic

nameplate data of the motor.

SP1.1 Motor Full Load Amps: Allows the user to enter the motor’s

FLA rating. Range of adjustment is 50 - 100% (less

programmed service factor).

SP1.2 Service Factor: Sets the pickup point on the overload curve

as defined by the programmed motor full load current. Ex:

If the motor FLA is 100 and the service factor is 1.15, the

overload pickup point will be 115 Amps.

SP1.3 Overload Class: Choose the motor protection overload class,

range from 5-30.

Ex: Overload Class 10 will trip in 10 seconds at six times

FLA.

SP1.4 NEMA design: The motor design maximum allowed slip

(Select from Class A through F).

SP1.5 Insulation Class: The motor insulation temperature class

(Select A, B, C, E, F, H, K, N or S).

SP1.6 Line Voltage Input: Applied Voltage

SP1.7 Line Frequency: The user may choose either 50 Hz or 60

Hz.

MENU

PAGE 1 BASIC
CONFIGURATION

MOTOR FULL LOAD AMPS
: 200 AMPS

SERVICE FACTOR
: 1.15 X FLA

OVERLOAD
CLASS: 10

NEMA
DESIGN: B

INSULATION
CLASS: B

LINE VOLTAGE
INPUT: 4160 VOLTS

Range: 50 - 100% of Unit
MAX CURRENT AMPS
Increments of 1

Range: 1.00 - 1.3
Increments of 0.01

Range: 5 - 30
Increments of 5

Range: A - F

Range: A - S

Range: 100 - 7200

LINE FREQUENCY
HZ: 60

Range: 50 or 60