Jksss+ series 2.3 - 4.2kv, Menu – Toshiba VF010H05 User Manual

Page 65

Advertising
background image

JKSSS+ Series - 59

JKSSS+ Series

2.3 - 4.2KV

SP.7 Custom Acceleration Curve (Setpoint Page 7)

(Security Level: 3)

MENU

PAGE 7 CUSTOM
ACCELERATION CURVE

CUSTOM ACCEL CURVE
: DISABLED

Range: DISABLED,
CURVE A, B or C

(Hit DOWN ARROW six times)

CURVE A VOLTAGE
LEVEL 1: 25%

CUSTOM CURVE A

CURVE A RAMP
TIME 1: 2 SEC

CURVE A RAMP
TIME 2: 2 SEC.

CURVE A VOLTAGE
LEVEL 3: 37%

CURVE A RAMP
TIME 3: 2 SEC.

CURVE A VOLTAGE
LEVEL 2: 30%

CURVE A VOLTAGE
LEVEL 4: 45%

CURVE A VOLTAGE
LEVEL 5: 55%

CURVE A RAMP
TIME 5: 2 SEC.

CURVE A VOLTAGE
LEVEL 6: 67%

CURVE A RAMP
TIME 4: 2 SEC.

CURVE A VOLTAGE
LEVEL 7: 82%

CURVE A RAMP
TIME 7: 2 SEC.

CURVE A RAMP
TIME 6: 2 SEC.

Range: 0 - 100%
Increments of 1

Range: 1 - 60 SEC
Increments of 1

Range: 0 - 100%
Increments of 1

Range: 1 - 60 SEC
Increments of 1

Range: 0 - 100%
Increments of 1

Range: 1 - 60 SEC
Increments of 1

Range: 0 - 100%
Increments of 1

Range: 1 - 60 SEC
Increments of 1

Range: 0 - 100%
Increments of 1

Range: 1 - 60 SEC
Increments of 1

Range: 0 - 100%
Increments of 1

Range: 1 - 60 SEC
Increments of 1

Range: 0 - 100%
Increments of 1

Range: 1 - 60 SEC
Increments of 1

SP7.1 Setpoint Page 7 allows the user to custom design

the acceleration curve (start curve) to the specific

application. The user can custom design up to

three different curves in the soft starter. Only one

curve can be active (enabled) at a time. Each of

the three curves allow for eight voltage plotting

points, with corresponding ramp times and a

current limit setting.

Note: Each successive voltage level must be

programmed to a voltage level equal to or greater

than the previous level. All eight levels of voltages

must be programmed and the eighth level has

been preset at 100%.

If Custom Accel Curve has been set to curve A,

B or C on this page, the soft starter will override

the Start Control Mode selected in Setpoint Page

2, (even if Start Control Mode in Setpoint Page 2

has not been set to Custom Accel Curve).

Note: Setpoint Page 7 has a security level 3

requirement.

Advertising