Operator interface – Trane CVHE-SVU01E-ENX39640712050 User Manual

Page 33

Advertising
background image

33

CVHE-SVU01E-EN

Operator
Interface

Reference

Top Level Mode

Sub Level Mode

BAS Code

Waiting To Start

Motor Temperature Inhibit: Motor Temperature / Inhibit Temperature

70

Waiting To Start

Restart Time Inhibit: MIN:SEC

70

Waiting To Start

High Vacuum Inhibit: Oil Sump Press / Inhibit Press

70

Waiting To Start

Low Oil Temperature Inhibit: Oil Temperature / Inhibit Temperature

70

Waiting To Start

Waiting For Starter To Start: MIN:SEC

70

Starting Compressor There is no sub mode displayed

72

Running

There is no sub mode displayed

74

Running

Hot Water Control

74

Running

Surge

74

Running

Base Loaded

74

Running

Hot Gas Bypass

74

Running

Ice Building

74

Running

Ice To Normal Transition

74

Running

Current Control Soft Loading

74

Running

Capacity Control Soft Loading

74

Running – Limit

Current Limit

75

Running – Limit

Phase Unbalance Limit

75

Running – Limit

Condenser Pressure Limit

75

Running – Limit

Evaporator Temperature Limit

75

Running – Limit

Minimum Capacity Limit

75

Running – Limit

Maximum Capacity Limit

75

Free Cooling

09

Free Cooling

Opening Free Cooling Valves

09

Free Cooling

Closing Free Cooling Valves

09

Preparing To
Shutdown

Closing IGV: IGV Position %

7E

Shutting Down

Post-Lubrication Time: MIN:SEC

7E

Shutting Down

Evaporator Pump Off Delay: MIN:SEC

7E

Shutting Down

Condenser Pump Off Delay: MIN:SEC

7E