Machine protection and adaptive control – Trane CVHE-SVU01E-ENX39640712050 User Manual

Page 81

Advertising
background image

81

CVHE-SVU01E-EN

Reset Ratio:

The Reset Ratio is displayed as a
percentage. To use it in the above
equation it must be converted to it’s
decimal form.

Reset Ratio percent /100 = Reset
Ratio decimal

Example of converting Reset Ratio:

If the Reset Ratio displayed on the
CLD is 50 percent then use (50/100)=
.5 in the equation

TOD = Outdoor Air Temperature

Start Reset = Outdoor Air Start Reset

Example of Calculating Reset for
Outdoor Air Temperature:

If:
Reset Ratio = 35 percent
Start Reset = 80
TOD = 65
Maximum Reset = 10.5

How many Degrees of Reset will
there be?

Degrees of Reset = Reset Ratio*(Start
Reset - TOD)
Degrees of Reset = .35*(80-65)
Degrees of Reset = 5.25

(* = multiply)

If:
Reset Ratio = -70 percent
Start Reset = 90
TOD = 100
Maximum Reset = 17

How many Degrees of Reset will
there be?

Degrees of Reset = Reset Ratio* (Start
Reset - TOD)
Degrees of Reset = -7* (90-100)
Degrees of Reset = 7

Figure 28. Outdoor air temperature versus degrees of reset

Machine Protection
and Adaptive
Control