CVHE-SVU01E-EN

48

Operator
Interface

The DynaView

Display Touch Screen Lock screen is shown below. This

screen is used if the Display and Touch Screen Lock feature is Enabled. 30
minutes after the last key stroke this screen will be displayed and the Display
and Touch Screen will be locked out until “159enter” is entered.
Until the proper password is entered there will be no access to the DynaView

screens including all reports, all setpoints, and Auto and Stop and Alarms and
Interlocks. The password “159” is not programmable from either DynaView

or TechView

.

If the Display and Touch Screen Lock feature is Disabled, the following screen
will be automatically shown if the MP temperature is below 32°F (0°C) and it
has been 30 minutes after the last key stroke.

Note: the main processor is

equipped with an on-board temperature sensor which enables the ice
protection feature.