CVHE-SVU01E-EN

Control System
Components

1A15, 1A16, 1A17, 1A21 Dual Analog
Input/output Module;
Analog Output:
The Analog Output is
a voltage only signal. 2-10 Vdc at
22mA

J2: 14 - 26 AWG with a maximum of
two 14 AWG

J2-1 Output #1 to J2-3 (Ground), J2-4
Output #2 to J2-6 (Ground).

UCP provides a 2-10 Vdc analog
signals as Outputs. The Output’s
maximum source capability is 22mA.
The maximum recommended length
to run this signal is included in the
table below.

Recommended Length to Run external Output signals

Gauge

Ohms per Feet

Length (Feet)

Maximum Length (Meters)

14

0.00 2823

1062.7

324

16

0.004489

668.3

203.8

18

0.007138

420.3

128.1

20

0.01135

264.3

80.6

22

0.01805

166.3

50.7

24

0.0287

104.5

31.9

26

0.04563

65.7

20

28

0.07255

41.4

12.6

Note: the above table is for copper conductors only.

Analog Input:
The analog input can be software
switched between a voltage input or
a current input. When used as a
current input a 200 Ohm load resistor
is switched in.

2-12 Vdc or 4 to 20 mA Analog Inputs
UCP accepts either a 2-10 Vdc or 4-20
analog input suitable for customer
external control. The type is
determined at unit commissioning
during feature installation.
J2: 14 - 26 AWG with a maximum of
two 14 AWG
J2-2 Input #1 to
J2-3 (Ground).
J2-5 Input #2 to
J2-6 (Ground).
Power, 24 +/- 10 percent VDC, 60 mA
maximum, Trane IPC3 protocol.