Machine protection and adaptive control – Trane CVHE-SVU01E-ENX39640712050 User Manual

Page 80

Advertising
background image

CVHE-SVU01E-EN

80

Table 3. Values for start reset types
The values for “RESET TYPE” are:
Reset

Outdoor

Return

Const Return

Type:

Disable

Air Reset

Reset

Reset

The values for “RESET RATIO” for each of the reset types are:
Reset

Reset

Increment

Increment

Factory

Type

Ratio

English

SI Units

Default

Range

Units

Value

Return

10 to 120 percent

1 percent

1 percent

50 percent

Outdoor -80 to 80 percent

1 percent

1 percent

10 percent

The values for “START RESET “ for each of the reset types are:
Reset

Start

Increment

Increment

Factory

Type

Reset

English

SI Units

Default

Range

Units

Value

Return

4 to 30°F

0.1°F

0.1°C

10°F (5.6°C)

(2.2 to 16.7°C)

Outdoor 50 to 130°F

0.1°F

0.1°C

90°F

(10 to 54.44°C)

(32.22°C)

The values for “MAXIMUM RESET” for each of the reset types are:
Reset

Maximum

Increment

Increment

Factory

Reset

English

SI Units

Default

Range

Units

Value

Return

0 to 20°F

0.1°F

0.1°C

5°F

(0.0 to 11.11°C)

(2.78°C)

Outdoor 0 to 20°F

0.1°F

0.1°C

5°F

(0.2 to 11.11°C)

(2.78°C)

Constant Return

CWS’ = CWS + 100 percent
(Design Delta Temperature) - (TWE-
TWL) and CWS’ > or = CWS and
CWS’ -CWS < or = Maximum Reset

Notice that Constant Return is
nothing more than a specific case of
Return Reset offered for operator
convenience.

When any type of CWR is enabled,
the UCP will step the CWS toward
the desired CWS (based on the above
equations and setup parameters) at a
rate of 1°F every 5 minutes until the
Active CWS equals the desired
CWS’. This applies when the chiller
is running only.

Using the Equation for calculating
CWR for Outdoor Air Temperature

Equation:
Degrees of Reset = Reset Ratio*(Start
Reset - TOD)

The chiller will start at the Differential
to Start value above a fully reset CWS
or CWS for both Return and Outdoor
Reset.

The graph on the next page, shows
the reset function for Outdoor Air
Temperature: Note: This graph
assumes that Maximum Reset is set
to 20 degrees.

Degrees of Reset:
Degrees of Reset = Active CWS -
Front Panel CWS
or
Degrees of Reset = CWS’ - CWS

To obtain Active CWS from Degrees
of Reset: Active CWS = Degrees of
Reset + Front Panel CWS

Machine Protection
and Adaptive
Control