1. Front Panel Control Type

(Chilled Water, Hot Water), Chilled Water default

2. Front Panel Chilled Water Setpoint

Temperature

1

3. Front Panel Hot Water Setpoint

Temperature

1

4. Front Panel Current Limit Setpoint

Percent

2

5. Front Panel Base Load Command

On or Auto

6. Front Panel Base Load Setpoint

Percent

7. Front Panel Free Cool Command

On or Auto

8. Front Panel Ice Building Command

On or Auto

9. Front Panel Ice Termination Setpoint

Temperature

10. Ice to Normal Cooling Timer

(0-10), 5 Minutes default

11. Differential to Start

Temperature

12. Differential to Stop

Temperature

13. Setpoint Source

*(BAS/EXT/FP, EXT/FP, FP), none default

*Follows hierarchy of selection from left to right (except ice build which is “OR” logic).

Mode Overrides
Description

Units

Default

Monitor Value

Notes

1. Compressor Control Signal

(Auto, Manual [0-100] ),

Auto

Percent Vane Position
Evaporator Leaving Water

7

Temperature, AFD Frequency, if installed

2. Evaporator Water Pump

(Auto, On),

Auto

1) Evaporator Flow status
2) Override Time Remaining

3

3. Condenser Water Pump

(Auto, On),

Auto

1) Condenser Flow status
2) Override Time Remaining

3

4. Oil Pump

(Auto, On),

Auto

1) Differential pressure
2) Override Time Remaining

3

5. Purge Exhaust Circuit Test

(Off, On),

Off

6. Purge Regeneration Cycle

(Off, On),

Off

Carbon Temperature

Feature Settings
Description

Units

1. Chilled Water Reset

(Constant, Outdoor, Return, Disable), Disable

2. Return Reset Ratio

Percent

3. Return Start Reset

Temperature

4. Return Maximum Reset

Temperature

5. Outdoor Reset Ratio

Percent

6. Outdoor Start Reset

Temperature

7. Outdoor Maximum Reset

Temperature

8. External Chilled Water Setpoint

(Enable, Disable), Disable

9. External Current Limit Setpoint

(Enable, Disable), Disable

10. Ice Building Feature Enable

(Enable, Disable), Disable

11. External Base Loading Setpoint

(Enable, Disable), Disable

Advertising