Control system components – Trane CVHE-SVU01E-ENX39640712050 User Manual

Page 52

Advertising
background image

CVHE-SVU01E-EN

52

Control System
Components

Control Panel Devices
Standard Devices

Controls

Field Connection

Description

Package

Purpose

Point Terminals

1A1 Power Supply

Standard

#1

Converts 24 vac to 24 vdc

not for field use

1A2 Power Supply

(as required) #2

Converts 24 vac to 24 vdc

not for field use

1A3 Dual Relay

Standard

Relay #1

Oil Heater Relay

not for field use

Output modules
1A4 Dual High

Standard

High Pressure Cutout

not for field use

Voltage Input
1A5 Quad Relay

Standard

Relay #1

Chilled water pump

J2-4 NO, J2-5 NC,

Output modules

(Relay #1)

J2-6 common

1A5 Quad Relay

Standard

Relay #2

Condenser water pump control

J2-1 NO, J2-2 NC,

Output modules

(relay #2)

J2-3 common

1A6 Dual High

Standard

Input 1

Condenser Flow Input

J2-2 Condenser water

Voltage Input

flow switch

1A6 Dual High

Standard

Input 2

Evaporator Flow Input

J3-2 Chilled water

Voltage Input

flow switch

1A7 High Power

Standard

Oil Pump and

not for field use

Output Relay

Refrigerant Pump

1A13 Dual LV Binary

Standard

Signal #1

External Auto Stop,

J2-1 Binary Input Signal #1,

input module

J2-2 Ground

1A13 Dual LV Binary

Standard

Signal #2

Emergency stop

J2-3 Binary Input Signal #2,

input module

J2-4 Ground

1A26*

Standard

Compressor Motor

not for field use

Winding Temp Sensor

1F1

Standard

LLID Power Supply Transformer

not for field use

Primary Circuit protection

1T1

Standard

Control Panel Power

not for field use

Transformer ; 120:24Vac

1Q1

Standard

Circuit Breaker - Compressor

not for field use

Motor Controller Control Power
Branch Circuit

1Q2

Standard

Circuit Breaker -

not for field use

Purge System Branch Circuit

1Q3

Standard

Circuit Breaker –

not for field use

Module [- LLID]
Power Supply Branch Circuit

1Q4

Standard

Circuit Breaker -

not for field use

Oil System Control
Branch Circuit

1Q5

Standard

Oil Pump Motor Branch

not for field use

Circuit protection

1X1 Terminal Block

Standard

Control Panel Terminal Block,

1X1-5 Chilled water flow

Flow switch connections

flow switch input
1X1-6 Condenser water flow
switch input

*previously was located in Purge Control Panel

Advertising