DynaView Interface

CG-SVU02B-E4

12

Chiller Level Mode

Top Level Mode

Description

Waiting to Start

The chiller is going through the necessary steps to allow the
lead circuit to start.

Waiting to Start Sub Modes

Description

Waiting For Condenser Water Flow

The chiller will wait a user adjustable time in this mode for
condenser water flow to be established per the flow switch
hardwired input.

Chiller Level Mode

Top Level Mode

Description

Running

At least one circuit on the chiller is currently running.

Running Sub Modes

Description

Maximum Capacity

The chiller is operating at its maximum capacity.

Capacity Control Softloading

The control is limiting the chiller loading due to capacity based
softloading setpoints.

Unit is Building Ice

The chiller is Building Ice, and will terminate on the Ice
Termination Setpoint based on the Entering Evap Water
Temperature sensor.

Chiller Level Mode

Top Level Mode

Description

Running - Limit

At least one circuit on the chiller is currently running, but the
operation of the chiller as a whole is being actively limited by
the controls. The sub modes that apply to the Running top
modes may also be displayed along with the following limit
specific modes.

Running - Limit Sub Modes

Description

Demand Limit

The number of compressors allowed to operate is being
limited to less than the available number of compressors by
either the BAS system, the front panel demand limit setpoint
or the external demand limit input.