Diagnostics – Trane CGWN 205-211 User Manual

Page 26

Advertising
background image

Diagnostics

CG-SVU02B-E4

26

Evaporator Entering Water
Temp Sensor

Chiller

Normal

Latch

All

Bad Sensor or LLID

Remote

Evaporator Leaving Water
Temp Sensor

Chiller

Normal

Latch

All

Bad Sensor or LLID

Remote

Condenser Entering Water
Temp Sensor

Chiller

Warning

Latch

All

Bad Sensor or LLID

Remote

Condenser Leaving Water
Temp Sensor

Chiller

Warning

Latch

All

Bad Sensor or LLID

Remote

Discharge Pressure
Transducer

Circuit

Normal

Latch

All

Bad Sensor or LLID

Remote

Suction Pressure Transducer

Circuit

Immediate

Latch

All

Bad Sensor or LLID

Remote

Suction Temperature Sensor

Circuit

Normal

Latch

All

Bad Sensor or LLID

Remote

Evaporator Protection Water
Temp Sensor

Circuit

Normal

Latch

All

Bad Sensor or LLID

Remote

Low Evap Leaving Water
Temp: Unit Off

Chiller or

Circuit

Warning

and Special

Action

NonLatch

Unit in Stop

Mode, or in

Auto Mode

and No

Ckt(s)

Energized

[Any Ckt

Energized]

a) The leaving chilled water temperature fell below the leaving
water temp cutout setting for 16.6°C- seconds while the Chiller
is in the Stop mode, or in Auto mode with no compressors
running. Energize Evap Water pump Relay until diagnostic auto
resets, then return to normal evap pump control. Automatic
reset occurs when the temp rises 1.1°C above the cutout
setting for 30 minutes. When this diagnostic is active AND
Leaving Water Temperature sensor diagnostic (loss of comm or
out of range) the Evap Water pump relay shall be de-energized.
b) If evaporator protection temperature sensors are installed,
the effect is on the appropriate circuit. Else, the effect is on the
chiller.

Remote

Low Evap Leaving Water
Temp: Unit On

Chiller or

Circuit

Immediate

and Special

Action

NonLatch

Any Ckt[s]

Energized
[No Ckt(s)

Energizd]

a) The chilled water temperature fell below the cutout setpoint
for 16.6°C-seconds while a compressor was running.
Automatic reset occurs when the temperature rises 1.1°C
above the cutout setting for 2 minutes. This diagnostic shall not
de-energize the Evaporator Water Pump Output. If this
diagnostic is active the Low Evap Leaving Water Temp: Unit Off
diagnostic shall be suppressed.
b) If evaporator protection temperature sensors are installed,
the effect is on the appropriate circuit. Else, the effect is on the
chiller.

Remote

Low Refrigerant
Temperature

Circuit

Immediate

Latch

All except

[Service

Pumpdown]

The Evaporator Saturated Refrigerant Temperature dropped
below the Low Refrigerant Temperature Cutout Setpoint for
16.6°C-seconds.

Local