Diagnostics – Trane CGWN 205-211 User Manual

Page 29

Advertising
background image

Diagnostics

29

CG-SVU02B-E4

Table 6 - Communication Diagnostics

Notes:
1. The following communication

loss diagnostics will not occur
unless that input or output is
required to be present by the
particular configuration and
installed options for the chiller.

2. Communication diagnostics

(with the exception of "Excessive
Loss of Comm" are named by
the Functional Name of the input
or output that is no longer being
heard from by the Main
Processor.

Many LLIDs, such as the Quad
Relay LLID, have more than one
functional output associated with
it. A comm loss with such a
multiple function board will
generate multiple diagnostics.
Refer to the Chiller's wiring
diagrams to relate the
occurrence of multiple
communication diagnostics back
to the physical llid boards that
they have been assigned to
(bound).

Diagnostic Name

Effects

Severity

Persistence

Active

Modes

[Inactive

Modes]

Criteria

Reset

Level

Excessive Loss of Comm

Chiller

Immediate

Latch

All

Loss of comm with 20% or more of the llids configured for the
system has been detected. This diagnostic will suppress the
callout of all subsequent comm loss diagnostics. Check power
supply(s) and power disconnects - troubleshoot LLIDS buss
using TechView

Remote

Comm Loss:
External Auto/Stop

Chiller

Normal

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.

Remote

Comm Loss:
Emergency Stop

Chiller

Normal

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.

Remote

Comm Loss:
Ext Ice Building Ctrl Input

Chiller

Warning

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period. Chiller
shall revert to normal (non-ice building) mode regardless of last
state.

Remote

Comm Loss:
Outdoor Air Temperature

Chiller

Warning

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period. If
configured as an air-cooled this diagnostic shall turn on all fans
and use a minimum LPC ignore time of 30 seconds.

Remote

Comm Loss:
Evap Leaving Water Temp

Chiller

Normal

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.

Remote

Comm Loss:
Evap Entering Water Temp

Chiller

Normal

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.

Remote

Comm Loss:
Condenser Leaving Water
Temp

Chiller

Warning

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.

Remote

Comm Loss:
Condenser Entering Water
Temp

Chiller

Warning

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.

Remote

Comm Loss:
Discharge Pressure
Transducer

Circuit

Normal

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.

Remote