Dynaview interface – Trane CGWN 205-211 User Manual

Page 13

Advertising
background image

DynaView Interface

13

CG-SVU02B-E4

Chiller Level Mode

Top Level Mode

Description

Shutting Down

The chiller is still running but shutdown is imminent. The
chiller is going through a compressor run-unload.

Shutting Down Sub Modes

Description

The Evaporator pump is executing the pump off delay timer.

The Condenser pump is executing the pump off delay timer.

Chiller Level Mode

Top Level Mode

Description

Misc.

These sub modes may be displayed in most of the top level
chiller modes

Misc. Sub Modes

Description

Cond Fans Inhibited By Low Pressure

The condenser fans are being inhibited from running because
the ambient temperature was below 10°C and the suction
pressure status is not good at startup for each circuit.

Hot Water Control

For water cooled (CGWN) the chiller is controlling to the
leaving condenser water temperature. For a reversible (CXAN)
the reversing valve is in the heating position. This sub-mode is
mutually exclusive with the Chilled Water Control mode.

Chilled Water Control

For water cooled (CGWN) the chiller is controlling to the
leaving evaporator water temperature. For a reversible (CXAN)
the reversing valve is in the cooling position. This sub-mode is
mutually exclusive with the Hot Water Control mode

Manual Evaporator Pump Override

The evaporator water pump relay is on due to a manual
command.

Diagnostic Evap Pump Override

The evaporator water pump relay is on due to a diagnostic.

Diagnostic Condenser Fan Override

The condenser fan relays are on due to a diagnostic.

Manual Condenser Pump Override

The condenser water pump relay is on due to a manual
command.

Manual Compressor Control Signal

Chiller capacity control is being controlled by DynaView or
TechView.

Anti-Freeze Heater On

The anti-freeze heater is on.

Evaporator Water Pump Off Delay:
MIN:SEC

Condenser Water Pump Off Delay:
MIN:SEC