Diagnostics – Trane CGWN 205-211 User Manual

Page 31

Advertising
background image

Diagnostics

31

CG-SVU02B-E4

Comm Loss:
Condenser Fan Control Relays

Circuit

Immediate

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.

Remote

Comm Loss:
Fan Fault

Chiller

Warning

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.

Remote

Comm Loss:
Op Status Programmable
Relays

Chiller

Warning

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.

Remote

Comm Loss:
Anti-Freeze Heater Relay

Chiller

Warning

and Special

Action

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.

Remote

Comm Loss:
Evap Protection Water Temp

Circuit

Normal

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.

Remote

Comm Loss:
Evaporator Water Pump 1 (or
Pump 2) Relay

Chiller

Warning

and Special

Action

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period. For
multi-pump systems, control switches to redundant pump.
Failure of both pump systems results in a normal shutdown.

Remote

Comm Loss:
Condenser Water Pump 1 (or
Pump 2) Relay

Chiller

Warning

and Special

Action

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period. For
multi-pump systems, control switches to redundant pump.
Failure of both pump systems results in a normal shutdown.

Remote

Comm Loss:
Evaporator Pump 1 (or
Pump 2) Fault Input

Chiller

Warning

and Special

Action

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period. For
multi-pump systems, control switches to redundant pump.
Failure of both pump systems results in a normal shutdown.

Remote

Comm Loss:
Condenser Pump 1 (or
Pump 2) Fault Input

Chiller

Warning

and Special

Action

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period. For
multi-pump systems, control switches to redundant pump.
Failure of both pump systems results in a normal shutdown.

Remote