DynaView Interface

15

CG-SVU02B-E4

Circuit Level Mode

Top Level Mode

Description

Running - Limit

The compressor on the given circuit is currently running in a
limit mode.

Running - Limit Sub Modes

Description

Hot Start Limit

Additional stages on a given circuit are being held off based
on leaving evaporator temperature.

Condenser Pressure Limit

The circuit is being inhibited from loading due to high
condenser pressure.

Low Evaporator Pressure Limit

The circuit is being inhibited from loading due to low
evaporator pressure.

Circuit Level Mode

Top Level Mode

Description

Preparing Shutdown

The circuit is preparing to de-energize the compressor.

Preparing Shutdown Sub Modes

Description

Operational Pumpdown

The operational pumpdown is enabled and the circuit is
shutting down.

Circuit Level Mode

Top Level Mode

Description

Shutting Down

The chiller is going through the necessary steps after de-
energizing the compressor.

Shutting Down Sub Modes

Description

No Circuit Sub-Modes

Circuit Level Mode

Top Level Mode

Description

Misc.

These sub modes may be displayed in most of the top level
circuit modes

Misc. Sub Modes

Description

Defrosting

The circuit is in a defrost operational mode.

Service Pumpdown

The circuit is currently performing a service pumpdown.

Compressor X Running

A specific compressor is running where X is A or B.

Restart Time Inhibit Cprsr X: MIN:SEC

If there is accumulated Restart Inhibit Time, it must expire
before the compressor is allowed to start. X is denoted as
compressor A or B.