DynaView Interface

CG-SVU02B-E4

14

Table 2 - Circuit Level Operating Modes:

Circuit Level Mode

Top Level Mode

Description

Stopped

The circuit is not running, and cannot run without
intervention.

Stopped Sub Modes

Description

Diagnostic Shutdown - Manual Reset

The circuit has been shutdown on a latching diagnostic.

Front Panel Circuit Lockout

The circuit is manually locked out by the circuit lockout setting
- the nonvolatile lockout setting is accessible through either
the DynaView or TechView.

Circuit Level Mode

Top Level Mode

Description

Run Inhibit

The given circuit is currently being inhibited from starting (and
running), but may be allowed to start if the inhibiting or
diagnostic condition is cleared.

Run Inhibit Sub Modes

Description

Diagnostic Shutdown - Auto Reset

The circuit has been shutdown on a diagnostic that may clear
automatically.

Condenser Pressure Limit

The circuit is being inhibited from starting due to high
condenser pressure.

Circuit Level Mode

Top Level Mode

Description

Auto

The circuit is not currently running but can be expected to
start at any moment given that the proper conditions are
satisfied.

Auto Sub Modes

Description

No Circuit Sub-Modes

Circuit Level Mode

Top Level Mode

Description

Waiting to Start

The chiller is going through the necessary steps to allow the
lead circuit to start.

Waiting to Start Sub Modes

Description

No Circuit Sub-Modes

Circuit Level Mode

Top Level Mode

Description

Running

The compressor on the given circuit is currently running.

Running Sub Modes

Description

No Circuit Sub-Modes