Diagnostics – Trane CGWN 205-211 User Manual

Page 30

Advertising
background image

Diagnostics

CG-SVU02B-E4

30

Comm Loss:
Suction Pressure Transducer

Circuit

Immediate

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.

Remote

Comm Loss:
Ext Chilled/Hot Wtr Setpoint

Chiller

Warning

and Special

Action

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period. Chiller
shall discontinue use of the External Chilled/Hot Water
Setpoint source and revert to the next higher priority for
setpoint arbitration

Remote

Comm Loss:
External Demand Limit
Setpoint

Chiller

Warning

and Special

Action

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period. Chiller
shall discontinue use of the External Demand Limit Setpoint
source and revert to the next higher priority for setpoint
arbitration

Remote

Comm Loss:
Auxiliary Setpoint Command

Chiller

Warning

and Special

Action

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period. Chiller
shall discontinue use of the Auxiliary Setpoint and revert to the
Chilled Water Setpoint based on setpoint arbitration

Remote

Comm Loss:
High Pressure Cutout Switch

Chiller

Immediate

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.

Remote

Comm Loss:
Evaporator Water Flow Switch

Chiller

Immediate

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.

Remote

Comm Loss:
Condenser Water Flow Switch

Chiller

Immediate

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.

Remote

Comm Loss:
Local BAS Interface

Chiller

Warning

and Special

Action

NonLatch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period. Use the
last values sent from BAS

Remote

Comm Loss:
Solenoid Valve

Circuit

Normal

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.

Remote

Comm Loss:
Motor Temp/Overload

Cprsr

Immediate

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.

Remote

Comm Loss:
Compressor Run Command

Cprsr

Immediate

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.

Remote

Comm Loss:
Protection Module Cprsr

Circuit

Warning

Latch

All

Continual loss of communication between the MP and the
Functional ID has occurred for a 35-40 second period.

Remote