Diagnostics – Trane CGWN 205-211 User Manual

Page 28

Advertising
background image

Diagnostics

CG-SVU02B-E4

28

Evaporator Water
Flow Lost Pump 1
(or Pump 2)

Chiller

Warning and

Special Action

NonLatch

Evap pump

commanded on

After flow had been proven the chilled water flow input
was open for more than 4 continuous seconds. The
evaporator pump control will switch control to the
redundant pump. If redundant pump is not available,
diagnostic will clear when flow is established.

Remote

Evaporator Water
Flow Overdue
Pump 1 (or
Pump 2)

Chiller

Warning and

Special Action

NonLatch

Estab. Evap. Water

Flow on going from

STOP to AUTO.

Evaporator water flow was not proven within a user
adjustable time of the evaporator water pump relay being
energized. Diagnostic is reset with return of evaporator
water flow.

Remote

Fault Detected:
Evaporator Water
Pump 1 (or
Pump 2)

Chiller

Warning and

Special Action

NonLatch

All

Detection of a pump fault will cause pump control to
switch to the redundant pump.

Remote

Condenser Water
Flow Lost Pump 1
(or Pump 2)

Chiller

Warning and

Special Action

NonLatch

Start and All Run

Modes

After flow had been proven the condenser water flow
input was open for more than 4 continuous seconds. This
diagnostic is automatically cleared once all circuits are de-
energized.

Remote

Condenser Water
Flow Overdue
Pump 1 (or
Pump 2)

Chiller

Warning and

Special Action

NonLatch

Estab Cond Water

Flow

Condenser water flow was not proven within a user
adjustable time of the condenser water pump relay being
energized.

Remote

Fault Detected:
Condenser Water
Pump 1 (or
Pump 2)

Chiller

Warning and

Special Action

NonLatch

All

Detection of a pump fault will cause pump control to
switch to the redundant pump.

Remote

Fan Fault

Circuit

Warning

NonLatch

All

The fan fault input was open for more than 5 seconds.

Local

High Condensing
Pressure Pump
Add

Chiller

Warning

Latch

Running

When running in parallel pump control, with one pump
on, a high condensing pressure will force add the second
pump. It will latch on to prevent pump cycling.

Remote