Version 1.0 March 1, 2000

P106 = ?

P107 = 60

P108 = xxxx

P115 = 1

P340 = 3

P383 = xxxx

P452 = 100

P106 = NEMA Motor Nameplated
efficiency (if unknown set =0.8)

P107 = Rated Motor Frequency

P108 = Nameplated Rotor RPM

P115 = 1
“Automatic Parameterization”

P340 = Carrier Frequency
Low # = Cooler Motor and Drive
High # = Lower Motor Noise

P383 = Motor Thermal Time
Constant. If constant unknown use
general guidelines;

2 Pole Motor = 480 seconds
4 Pole Motor = 600 seconds
6 Pole Motor = 720 seconds

P452 = Maximum Forward Speed in
Percentage (usually 100%)