2.2 Basic Start-up (Regenerative Rectifier without

Autotransformer)

P051 = 2

P053 = 6

P052 = 5

P071 = 460

P320 = 20

P773 = 1.00

P051=2

Select “Basic Mode Settings”

P053 =6 Access Parameter

P052 = 5

Drive Settings

P071 = Input Rectifier Voltage

Generally = 460 Volt

P320 = 20

Smooth Load Amps, to
prevent input line sags
from effecting the DC BUS
regulator

P773= 1.00

Deadband Converter, to
prevent “toggling” between
Regen and Rectifier
bridges.