3 vector control without encoder feedback, P100 = 3, Wait – Vector 6SE70 VC User Manual

Page 24

Advertising
background image

Page 24

Version 1.0 March 1, 2000

1.3.3 Vector Control without Encoder Feedback

Note: Complete section 1.3.1 (Volts/Hz control without encoder feedback).

P060 = 5

P100 = 3

P060 = 1

P115 = 4

Wait

P060=5

Select “Drive Settings”

P100=3

Selects Vector Control
without Encoder Feedback

P060 = Return to Parameter Menu
If you plan to use an encoder, go to
section1.3.4, otherwise continue.

P115 = 4 No-Load Measurement
Uncoupled motor will ROTATE.
Alarm message “A080” will appear,
and a start command must be issued
within 20 seconds to perform the test,
otherwise P115 will unset.

This test will adjust the following
parameters

P103, P120

Wait for display to change back
to

o

009.

Advertising