P453 = -100

P060 = 1

P128 = xxxx

P462 = xxxx

P464 = xxxx

P443i2= 11

P453 = Maximum Reverse Speed in
Percentage (usually -100%)

P060 = Return to Parameter Menu

P128 = Maximum Motor Current
Options:

P128 = P102
P128=1.1*P102
P128=1.5*P102

P462 = Acceleration Time in seconds

P464 = Deceleration Time in seconds

P443i2(Index2) = 11
Configures drive for analog input
(0-10Vdc) to be active at
terminals X101 pin#15 and
pin#16

If 4-20mA is required closed
CUVC board mounted jumper
S3, position 1 and 2.

Start/Stop Control is located on
the PMU (operator control panel
mounted directly on the drive)

Speed Setpoint is controlled with
the Up / Down arrows.