1.3.4 Vector Control with Encoder Feedback

Note: Complete section 1.3.1 (Volts/Hz control without encoder feedback), and
section 1.3.3 (Vector control without encoder feedback)

Step 10: Operate the uncoupled motor if sections 1.3.1 and 1.3.3 are complete and
verify operation of the motor without faults.

P060 = 5

P100 = 4

P130 = ?

P151 = ?

P060 = 1

P115 = 4

P060=5

Select “Drive Settings”

P100=4

Selects Vector Control
with Encoder Feedback
Connect encoder as per
diagram

P130 = Select Type of Encoder

11: Pulse Encoder
15: Pulse Encoder with Zero Pulse

P151 = Pulse Per Revolution (PPR)

P060 = Return to Parameter Menu

P115 = 4 No-Load Measurement
Uncoupled motor will ROTATE.
Alarm message “A080” will appear,
and a start command must be issued
within 20 seconds to perform the test,
otherwise P115 will unset.