Page 46

Version 1.0 March 1, 2000

P571 = 0

P318 = 95

P052 = 21

P052 = 0

P571=0 Selects Autotransformer

P318 = 95%

Selects percentage of nominal
DC BUS voltage. In cases where
the input line voltage is
dependable a setting of 100% is
permissible.

With DC BUS connected to the
COMMON DC BUS of the system, set
P52=21 and provide a start command
at terminal X101, pin #9

The circuit identification test will take
about 10 seconds.

P052=0 Drive back to ready mode.

Standard Commissioning for a
Regenerative Rectifier with
Autotransformer is complete, after
adjusting only 10 parameters.