Terminal definitions for slots a and b – Watlow Electric Integrated Controller User Manual Rev C EZ-ZONE PM User Manual

Page 13

Advertising
background image

Wa t l o w E Z - Z O N E

®

P M I n t e g r a t e d C o n t r o l l e r

1 1

C h a p t e r 2 I n s t a l l a n d W i r e

Slot A

Slot B

Output

Terminal Function

Configuration

1

2

3

4

X1

W1

Y1

X3

W3

Y3

common (Any switched dc output can use this common.)
dc- (open collector)
dc+

Switched dc/open collector
output 1: PM6 _ _ C _-_ _ _ _ A _ _
output 3: PM6 _ _ _ _-_ _ C _ A _ _

W2

Y2

W4

Y4

dc-
dc+

Switched dc
output 2: PM6 _ _ _ C-_ _ _ _ A _ _
output 4: PM6 _ _ _ _-_ _ _ C A _ _

F1

G1
H1

F3

G3
H3

voltage or current -
voltage +
current +

Universal Process
output 1: PM6 _ _ F _-_ _ _ _ A _ _
output 3: PM6 _ _ _ _-_ _ F _ A _ _

L1

K1

J1

L3

K3

J3

normally open
common
normally closed

Mechanical Relay 5 A, Form C
output 1: PM6 _ _ E _-_ _ _ _ A _ _
output 3: PM6 _ _ _ _-_ _ E _ A _ _

L2

K2

normally open
common

No-arc 15 A, Form A
output 2: PM6 _ _ _ H-_ _ _ _ A _ _

L2

K2

L4

K4

normally open
common

Mechanical Relay 5 A, Form A
output 2: PM6 _ _ _ J-_ _ _ _ A _ _
output 4: PM6 _ _ _ _-_ _ _ J A _ _

L1

K1

L2

K2

L3

K3

L4

K4

normally open
common

Solid-state Relay 0.5 A, Form A
output 1: PM6 _ _ K _-_ _ _ _ A _ _
output 2: PM6 _ _ _ K-_ _ _ _ A _ _
output 3: PM6 _ _ _ _-_ _ K _ A _ _
output 4: PM6 _ _ _ _-_ _ _ K A _ _

Communications

CB
CA
CC
CB
CA

C5
C3
C2

Modbus RTU EIA-485 T+/R+
Modbus RTU EIA-485 T-/R-
Modbus RTU EIA-485 common
Modbus RTU EIA-485 T+/R+
Modbus RTU EIA-485 T-/R-
Modbus RTU EIA-232 common
Modbus RTU EIA-232 to DB9 pin 2
Modbus RTU EIA-232 to DB9 pin 3

Modbus RTU 232/485 Communications
PM6 _ _ _ _-2 A A A A _ _

V+

CH

SH

CL

V-

DeviceNet™ power
Positive side of DeviceNet™ bus
Shield interconnect
Negative side of DeviceNet™ bus
DeviceNet™ power return

DeviceNet™ Communications
PM6 _ _ _ _-5 A A A A _ _

E8
E7
E6
E5
E4
E3
E2
E1

EtherNet/IP™ and Modbus TCP unused
EtherNet/IP™ and Modbus TCP unused
EtherNet/IP™ and Modbus TCP receive -
EtherNet/IP™ and Modbus TCP unused
EtherNet/IP™ and Modbus TCP unused
EtherNet/IP™ and Modbus TCP receive +
EtherNet/IP™ and Modbus TCP transmit -
EtherNet/IP™ and Modbus TCP transmit +

Ethernet 10/100 supporting EtherNet/IP™
and Modbus TCP
PM6 _ _ _ _-3 A A A A _ _

Inputs

1

2

T1
S1
R1

T2
S2
R2

S2 (RTD) or current +, potentiometer wiper
S3 (RTD), thermocouple -, current - or volts -
S1 (RTD), thermocouple + or volts +

Universal Sensor

input 1: all configurations

input 2: PM6 _ _ _ _-_ (R or L) _ _ A _ _

T2
S2

mA ac
mA ac

Current Transformer

PM6 _ _ _ _-_ T _ _ A _ _

Terminal Definitions for Slots A and B.

Slot A

Slot B

Slot C

or

Output 1

Output 2

Input 1

Output 3

Output 4

Input 2

Power

485 Comms

Dig I/O 5 & 6

Communications

Slot B

Advertising