Wa t l o w E Z - Z O N E

®

P M I n t e g r a t e d C o n t r o l l e r

4 0

C h a p t e r 6 S e t u p P a g e

Dis-

play

Parameter Name

Description

Set-

tings

Range

Default

Appears If

[``Fn]
[ Fn]

Output (1 to 4)
Function

Select what function will drive this output.

[`oFF] Off
[hEAt] Heat
[CooL] Cool
[ALM] Alarm
[`Ent] Event
[LiM] Limit (outputs 3 & 4)

Heat

Alarm

Off (outputs 3

& 4)

a time-proportioned out-

put (solid-state relay,
switched dc or mechani-
cal relay)

[``Fi]
[ Fi]

Output (1 to 4)
Function Instance

Select which source instance will drive the
output.

1 to 4

1

a time-proportioned out-

put (solid-state relay,
switched dc or mechani-
cal relay), and there is
more than one instance
of the Function selec-
tion.

[`o;Ct]
[ o.Ct]

Output (1 to 4)
Control

Set the output control type. This param-
eter is only used with PID control, but can
be set anytime.

[`Ftb] Fixed Time Base
[`utb] Variable Time Base

Fixed Time

Base

a time-proportioned out-

put (solid-state relay,
switched dc or mechani-
cal relay).

If output 1 is a universal

process output, output
2 cannot function as
a variable-time-base
output. If output 3 is
a universal process
output, output 4 cannot
function as a variable-
time-base output.

[`o;tb]
[ o.tb]

Output (1 to 4)
Time Base

Set the time base for fixed-time-base con-
trol.

0.1 to 60.0 seconds (solid-

state relay or switched dc)

5.0 to 60.0 seconds (mechani-

cal relay or no-arc power
control)

0.1 sec. [SSR &

sw dc]

20.0 sec.

[mech, relay,
no-arc]

a time-proportioned

output (solid-state
relay, switched dc or
mechanical relay) and
Control is set to Fixed
Time Base.

[`o;Lo]
[ o.Lo]

Output (1 to 4)
Low Power Scale

The power output will never be less than
the value specified and will represent the
value at which output scaling begins.

0.0 to 100.0%

0.0%

a time-proportioned out-

put (solid-state relay,
switched dc or mechani-
cal relay) and Source is
set to Heat or Cool.

[`o;hi]
[ o.hi]

Output (1 to 4)
High Power Scale

The power output will never be greater
than the value specified and will represent
the value at which output scaling stops.

0.0 to 100.0%

100.0%

a time-proportioned out-

put (solid-state relay,
switched dc or mechani-
cal relay) and Source is
set to Heat or Cool.

[Alm]

[```1] [```2] [```3] [```4]

[`Set]

[Alm] [Alm] [Alm] [Alm]

Alarm Menu

Alarm 1

Alarm 2

Alarm 3

Alarm 4

[`A;ty]
[ A.ty]

Alarm (1 to 4)
Type

Select how the alarm will or will not track
the set point.

[`oFF] Off
[PR;AL] Process Alarm
[dE;AL] Deviation Alarm

Off

always

[`sr;a]
[ Sr.A]

Alarm (1 to 4)
Source

Select what will trigger this alarm.

[``Ai] Analog Input
[PWr] Power (process only)
[CUrr] Current (process only)

Analog Input

always

[`is;a]
[ iS.A]

Alarm (1 to 4)
Source Instance

If Alarm Source is set to input, select
which input to use.

1 or 2

1

there is more than one

instance of the Source
selection.

Note: Some values will be rounded off to fit in the four-character display. Full values can be read with other interfaces.

If there is only one instance of a menu, no submenus will appear.