Dis-

play

Parameter Name

Description

Set-

tings

Range

Default

Appears If

[`A;hy]
[ A.hy]

Alarm (1 to 4)
Hysteresis

Set the hysteresis for an alarm. This de-
termines how far into the safe region the
process value needs to move before the
alarm can be cleared.

0.001 to 9,999.000°F or units

0.001 to 5,555.000°C

1.0°F or units

1.0°C

always

[`A;Lg]
[ A.Lg]

Alarm (1 to 4)
Logic

Select what the output condition will be
during the alarm state.

[`AL;C] Close On Alarm
[`AL;o] Open On Alarm

Close On

Alarm

always

[`A;Sd]
[ A.Sd]

Alarm (1 to 4)
Sides

Select which side or sides will trigger this
alarm.

[both] Both
[high] High
[LoW] Low

Both

always

[`A;LA]
[ A.LA]

Alarm (1 to 4)
Latching

Turn alarm latching on or off. A latched
alarm has to be turned off by the user.

[nLAt] Non-Latching
[`LAt] Latching

Non-Latching

always

[`A;bL]
[ A.bL]

Alarm (1 to 4)
Blocking

Select when an alarm will be blocked.
After startup and/or after the set point
changes, the alarm will be blocked until
the process value enters the normal range.

[`oFF] Off
[`Str] Startup
[StPt] Set Point
[both] Both

Off

always

[`A;Si]
[ A.Si]

Alarm (1 to 4)
Silencing

Turn alarm silencing on to allow the user
to disable this alarm.

[`oFF] Off
[``on] On

Off

always

[A;dSP]
[A.dSP]

Alarm (1 to 4)
Display

Display an alarm message when an alarm
is active.

[`oFF] Off
[``on] On

On

always

[`A;dL]
[ A.dL]

Alarm (1 to 4)
Delay

Set the time the alarm will be delayed
after the process value exceeds the alarm
set point.

0 to 9,999 seconds

0

always

[CUrr]
[`Set]
Current Menu

(menu appears if PM6 _ _ _ _-_ T _ _ A _ _)

[`C;Sd]
[ C.Sd]

Current
Sides

Select which side of the current to monitor.

[`oFF] Off
[high] High
[LoW] Low
[both] Both

Off

always

[`CU;r]
[ CU.r]

Current
Reading Enable

Display under- or over-range current.

[``no] No
[`YES} Yes

No

always

[`C;dt]
[ C.dt]

Current
Detect Threshold

For factory adjustment only.

3 to 59

9

always

[`C;SC]
[ C.SC]

Current
Scaling

Adjust scaling to match the transformer's
high range.

0 to 9,999.000 amperes

50.0

always

[C;oFS]
[C.oFS]

Current
Offset

Calibrate the current reading with an
offset value.

-1,999.000 to 9,999.000

0.0

always

Note: Some values will be rounded off to fit in the four-character display. Full values can be read with other interfaces.