Output 1 solid-state relay, form a, Output 2 switched dc, Output 2 no-arc relay, form a – Watlow Electric Integrated Controller User Manual Rev C EZ-ZONE PM User Manual

Page 20: Output 2 mechanical relay, form a

Advertising
background image

Ó

Warning:
Use National Electric (NEC)
or other country-specific
standard wiring and safety
practices when wiring and
connecting this controller to
a power source and to elec-
trical sensors or peripheral
devices. Failure to do so may
result in damage to equip-
ment and property, and/or
injury or loss of life.

Note:
Maximum wire size termina-
tion and torque rating:
• 0.0507 to 3.30 mm2 (30 to
12 AWG) single-wire termi-
nation or two 1.31 mm2 (16
AWG)
• 0.8 Nm (7.0 lb.-in.) torque

Note:
Adjacent terminals may be
labeled differently, depend-
ing on the model number.

Note:
To prevent damage to the
controller, do not connect
wires to unused terminals.

Note:
Maintain electrical isolation
between analog input 1, digi-
tal input-outputs, switched
dc/open collector outputs and
process outputs to prevent
ground loops.

Note:
The control output common
terminal and the digital com-
mon terminal are referenced
to different voltages and
must remain isolated.

Wa t l o w E Z - Z O N E

®

P M I n t e g r a t e d C o n t r o l l e r

1 8

C h a p t e r 2 I n s t a l l a n d W i r e

Output 1 Solid-state Relay, Form A

normally open

common

L1

K1

L2

K2

T1

S1

R1

Slot A

• 0.5 A at 20 to 264V

Å (ac) maxi-

mum resistive load

• 20 VA 120/240V

Å (ac) pilot duty

• opto-isolated, without contact

suppression

• maximum off state leakage of

105 microamperes

• output does not supply power
• Do not use on dc loads.
• See Quencharc note.
PM6 _ _ K _-_ _ _ _ A _ _

Internal Circuitry

common

normally

open

Solid-state Relay

L1

K1

Output 2 Switched DC

dc+

dc-

L1

K1

J1

W2

Y2

T1

S1

R1

Slot A

• 10 mA DC maximum supply

current

• short circuit limited to <50 mA
• 22 to 32V

Î (dc) open circuit

voltage

• use dc- and dc+ to drive exter-

nal solid-state relay

• DIN-A-MITE compatible
• single-pole: up to 2 in series,

none in parallel

PM6 _ _ _ C-_ _ _ _ A _ _

Internal
Circuitry

dc-

dc+

Load

Switched DC

-

+

W2

Y2

Output 2 No-arc Relay, Form A

common

normally open

L1

K1

J1

L2

K2

T1

S1

R1

Slot A

• 15 A at 85 to 264V

Å (ac) resis-

tive load only

• 2,000,000 cycle rating for no-arc

circuit (preliminary)

• 100 mA minimum load
• 2 mA maximum off state leakage
• Do not use on dc loads.
• Output does not supply power.
PM6 _ _ _ H-_ _ _ _ A _ _

Output 2 Mechanical Relay, Form A

common

normally open

L1

K1

J1

L2

K2

T1

S1

R1

Slot A

• 5 A at 240V

Å (ac) or 30VÎ (dc)

maximum resistive load

• 20 mV at 24V minimum load
• 125 VA pilot duty @ 120/240V

Å

(ac), 25 VA at 24V

Å (ac)

• 100,000 cycles at rated load
• Output does not supply power.
• for use with ac or dc
See Quencharc note.
PM6 _ _ _ J-_ _ _ _ A _ _

Internal
Circuitry

common

normally

open

Mechanical

Relay

L2

K2

Quencharc Note:
Switching pilot duty inductive
loads (relay coils, solenoids,
etc.) with the mechanical
relay, solid state relay or
open collector output options
requires use of an R.C. sup-
pressor.

Advertising