Solid-State Relay
• 0.5 A @ 24 to 264V

Å (ac) maximum, opto-isolated, without con-

tact suppression; maximum off-state leakage current: 105 micro-
amperes

Electromechanical Relay, Form A
• 5 A, 24 to 240V

Å (ac) or 30VÎ (dc) maximum, resistive load,

100,000 cycles at rated load, 125 VA pilot duty

• Requires a minimum load of 20 mA @ 24V

Electromechanical Relay, Form C
• 5 A, 24 to 240V

Å (ac) or 30VÎ (dc) maximum, resistive load,

100,000 cycles at rated load, 125 VA pilot duty

• Requires a minimum load of 20 mA @ 24V

No-arc Relay Form A
• 15 A, 85 to 264V

Å (ac), no VÎ (dc), resistive load, 2 million cycles

at rated load (preliminary), maximum off-state leakage current:
2 mA

Process
• Universal process/Retransmit, outputs range selectable, 0 to 10

V

Î (dc) into minimum 1,000 Ω load, 0 to 20 mA into maximum

800 Ω load

Operator Interface

• Dual 4-digit, 7-segment LED displays
• Advance, infinity, up and down keys plus an EZ Key program-

mable function key

• Typical display update rate 1Hz
• Agency approved to IP66/NEMA 4X

Dimensions

Size

Behind

Panel

(max.)

Width

Height

Display Height

1/16

101.6 mm
(4.00 in)

53.3 mm
(2.10 in)

53.3 mm
(2.10 in)

up: 10.80 mm (0.425 in)
low: 6.98 mm (0.275 in)

Weight

• Controller: 200 g (7.1 oz.)
• User manual: 167.26 g (5.9 oz)

Modbus® is a trademark of AEG Schneider Automation Inc.

EtherNet/IP™ is a trademark of ControlNet International Ltd. used
under license by Open DeviceNet Vendor Association, Inc. (ODVA).

UL® is a registered trademark of Underwriters Laboratories Inc.

DeviceNet™ is a trademark of Open DeviceNet Vendors Associatlon.

Note: These specifications are subject to change without prior
notice.