Ez-zone – Watlow Electric Integrated Controller User Manual Rev C EZ-ZONE PM User Manual

Page 6

Advertising
background image

Wa t l o w E Z - Z O N E

®

P M I n t e g r a t e d C o n t r o l l e r

4

C h a p t e r 1 O v e r v i e w

EZ-ZONE

®

PM Integrated Model 1/16 DIN with a Current Transformer — Input/Output

(no communications options 2 to 3)

Universal Sensor Input, Configuration Communications,

Red/Green 7-Segment Display

Supervisory

&

Power

Board

Slot C

PID

Controller

Board

Slot A

ramp-soak
with 4 files

(optional)

Output 4 none, switched dc, form A
mechanical (5 A) or solid-state (0.5 A)
relay

Output 3 none, switched dc/open
collector, form C mechanical (5 A) or
solid-state (0.5 A) relay, process (V, mA)

Output 2 none, switched dc, no-arc
power control (15 A), form A mechanical
(5 A) or solid-state (0.5 A) relay

Output 1 none, switched dc/open
collector, form C mechanical (5 A) or
solid-state (0.5 A) relay, process (V, mA)

off, heat, cool,
duplex, alarm,

retransmit,

event

off, heat, cool,

alarm, event

off, heat, cool,

alarm, event,

retransmit

off, heat, cool,

alarm, event

EZ Key
programmable event

Digital Output (or Input) 5 (optional)
none, switched dc

Digital Output (or Input) 6 (optional)
none, switched dc

off, heat, cool,

alarm, event

off, heat, cool,

alarm, event

Network
remote user interface,
personal computer,
programmable logic
controller, human-
machine interface

EIA 485 Communications
Standard Bus, Modbus RTU (optional)

Current

Transformer

Board

(optional)

Slot B

Analog Input 1 thermocouple,
RTD, process (V, mV, mA, 1k po-
tentiometer)

Digital Input (or Output) 5
(optional)

none, switch, volts dc

Digital Input (or Output) 6
(optional)

none, switch, volts dc

Analog Input 2
current transformer

none,
idle set point,
alarm reset,
tune,
silence alarm,
manual/auto mode,
control outputs off,
lock keypad,
force alarm,
TRU-TUNE+

®

disable

loop & alarms off,
profile disable,
profile hold/resume,
profile start,
profile start/stop,
restore user settings

current transformer

input sensor

Input

Functions

Output

Functions

Current Monitoring

detects heater current flow

provides an alarm indication of a failed-load issue.

Advertising