Indication

Description

Possible Cause(s)

Corrective Action

Process doesn’t con-

trol to set point

Process is unstable or never

reaches set point

• Controller not tuned correctly

• Perform autotune or manually tune

system

• Control mode is incorrectly set

• Set control mode appropriately (Open

vs Closed Loop)

• Control set point is incorrect

• Set control set point in appropriate

control mode and check source of set
point: remote, idle, profile, closed loop,
open loop

Temperature runway Process value continues to

increase or decrease past set
point.

• Controller output incorrectly pro-

grammed

• Verify output function is correct (heat

or cool)

• Thermocouple reverse wired

• Correct sensor wiring (red wire nega-

tive)

• Controller output wired incorrectly

• Verify and correct wiring

• Short in heater

• Replace heater

• Power controller connection to con-

troller defective

• Replace or repair power controller

• Controller output defective

• Replace or repair controller

[`100] Device Error
[rEtn]

Controller displays internal

malfunction message at
power up.

• Controller defective

• Replace or repair controller

[`h;Er] Heater Error Heater Error

• Current through load is above current

trip set point

• Check that the load current is proper.

Correct cause of overcurrent and/or en-
sure current trip set point is correct.

• Current through load is below current

trip set point

• Check that the load current is proper.

Correct cause of undercurrent and/or
ensure current trip set point is correct.

[`C;Er]
Current Error

Load current incorrect.

• Shorted solid-state or mechanical

relay

• Replace relay

• Open solid-state or mechanical relay

• Replace relay

• Current transformer load wire associ-

ated to wrong output

• Route load wire through current

transformer from correct output, and
go to the

[`C;Si] Source Output In-

stance parameter (Setup Page, Current
Menu) to select the output that is driv-
ing the load.

• Defective current transformer or con-

troller

• Replace or repair sensor or controller

• Noisy electrical lines

• Route wires appropriately, check for

loose connections, add line filters

Menus inaccessible

Unable to access

[`SEt],

[OPEr], [FCty] or [ProF]
menus or particular prompts
in Home Page

• Security set to incorrect level

• Check lockout setting in Factory Page

• Digital input set to lockout keypad

• Change state of digital input

• Custom parameters incorrect

• Change custom parameters in Factory

Page

EZ-Key doesn’t work

EZ-Key does not activate re-

quired function

• EZ-Key function incorrect

• Verify EZ-Key function in Setup Menu

• EZ-Key function instance not incor-

rect

• Check that the function instance is

correct

• Keypad malfunction

• Replace or repair controller