10

VEGASEL

Electrical connections

Transistor outputs in conjunction with a DCS/PLC

The resistor R

S

is used as current limitation to 60 mA

Example:

U

B

= 24 V, U

CE

1,5 V, I

B

= max. 60 mA

U

B

– U

CE

24 V – 1,5 V

R

S

= ––––––––– = –––––––––––– = 375

, selected 390

I

B

60 mA

Dissipated energy P

V

= I

2

• R

S

= 60 mA

2

• 390

= 1,404 W, selected 1,5 W

Example of a measuring system with VEGASEL 544

+

-

-

+

+

-

+

I

B

R

S

E 1.0

E 1.1

U

B

U

CE

I

B

U

CE

R

S

VEGATOR 544

DCS/PLC

e.g. magnet valve

e.g. pump

VEGASEL 544

VEGAMET 513

Pressure

transmitter

2

6

20

10

18

d b z

+

-

2

20

18

30

32

d b z

+

-

+

-

+

-

+

-

+

-

1

+

+

-

2

-

L
N

Schedule
U

B

R

S

5 V

58

12 V

180

24 V

390

36 V

680