Set-up

Two-point level switch (VEGASEL 543, 545, 547)

Coded key
max.

Coded key

min.

Mode A
Relay 1

LED 1

off

off

on

on

The above figure is also valid for VEGASEL 547 with 2 relays.

The feature of a two-point level switch is the hysteresis between the switching to on/off at two different points of
the input signal. The switch points and therefore the hysteresis are adjusted via the coded keys in the front panel
between 1 % and 99 %. With VEGASEL as two-point level switch the automatic filling and emptying of a vessel
can be controlled, or overfill protection and protection against dry running of pumps can be obtained.

With the coded keys, the %-values are adjusted which relate to the

of the input signal.

Example:

Input 4 … 20 mA, Switch point at 75 % and at 25 %

= 20 mA – 4 mA = 16 mA

75 % of 16 mA = 12 mA
25 % of 16 mA = 4 mA

Switch point 75 % corresponds to 4 mA + 12 mA = 16 mA

Switch point 25 % corresponds to 4 mA + 4 mA = 8 mA

If both coded keys are set to the same value, a single point level switch is obtained with a hysteresis of
approx. 0,5 %.